Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz) MCAC-ATSM-2013-11
104
operate.
No
Model
Max unit combined
quantity
L(mm)
M(mm)
N(mm)
1
MGCSL-F30W/RN1
1
≥
600
≥
300
≥
300
2
MGCSL-D30W/RN1
1
≥
600
≥
300
≥
300
3
MGCL-F30W/RN1
16
≥
600
≥
300
≥
300
4
MGCL-D30W/RN1
16
≥
600
≥
300
≥
300
5
MGBL-F65W/RN1
16
≥
600
≥
300
≥
300
6
MGBL-D65W/RN1
16
≥
600
≥
300
≥
300
7
MGBL-F130W/RN1
8
≥
600
≥
300
≥
300
8
MGBL-F200W/RN1
5
≥
600
≥
300
≥
300
9
MGBL-F250W/RN1
8
≥
600
≥
300
≥
300
12.1.3 Installation Foundation
The unit should be located on the horizontal foundation, the ground floor or the roof which can bear
operating weight of the unit and the weight of maintenance personnel. Refer to the operating weight
parameters in specification table.
If the unit is located so high that it is inconvenient for maintenance personnel to conduct maintenance,
the suitable scaffold can be provided around the unit.
The scaffold must be able to bear the weight of maintenance personnel and maintenance facilities.
The bottom frame of the unit is not allowed to be embedded into the concrete of installation foundation.
Location drawing of installation foundation of the unit
(unit: mm)