Table of diameter parameters of main inlet and outlet pipes for 200kW module
Unit model x quantity
Total inlet and outlet water
pipe diameter
Unit model x quantity
Total inlet and outlet water
pipe diameter
200×1
DN80
200×4
DN150
200×2
DN100
200×5
DN200
200×3
DN125
Table of diameter parameters of main inlet and outlet pipes for250kW module
Unit model x quantity
Total inlet and outlet water
pipe diameter
Unit model x quantity
Total inlet and outlet water
pipe diameter
250×1
DN100
250×5
DN150
250×2
DN100
250×6
DN200
250×3
DN125
250×7
DN250
250×4
DN150
250×8
DN250
Please pay attention to the following items when installing multiple modules:
● Each module corresponds to an address code which cannot be repeated.
● Main water outlet temperature sensing bulb, water flow switch and auxiliary electric heater are under
control of the main module.
● One wired controller and one water flow switch are required and connected on the main module.
● The unit can be started up through the wired controller only after all addresses are set and the
aforementioned items are determined. The wired controller is
≤50m away from the outdoor unit.
12.2.9 Chilled water flow
Minimum chilled water flow
The minimum chilled water flow is shown in the below table.
If the system flow is less than the minimum unit flow rate, the evaporator flow can be recalculated, as shown
in the diagram.
Maximum chilled water flow
The maximum chilled water flow is limited by the permitted pressure drop in the evaporator. It is provided in
the below table.
If the system flow is more than the maximum unit flow rate, bypass the evaporator as shown in the diagram
to obtain a lower evaporator flow rate.
Minimum and Maximum water flow rates
Item
Water flow rate(m3/h)
Model
Minimum
Maximum
MGCL-F30W/RN1
4.64
5.68
MGCL-D30W/RN1
MGCSL-F30W/RN1
4.68
5.72
MGCSL-D30W/RN1
4.68
5.72
MGBL-F65W/RN1
10.08
12.32
Evaporator
Recirculation
For minimum chilled water flow rate
Fig. 4-2
For maximum chilled water flow rate
Evaporator
Recirculation
Summary of Contents for Aqua Tempo Super Series
Page 48: ......
Page 62: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 61...
Page 69: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 68...
Page 72: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 71...