Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz) MCAC-ATSM-2013-11
98
12 Installation
12.1 Unit Installation
12.1.1 Transportation
The angle of inclination should not be more than 15º when carrying the unit, to avoid overturn of the unit.
a. Rolling handling: several rolling rods of the same size are placed under the base of the unit, and the
length of each rod must be more than the outer frame of the base and suitable for balancing of the unit.
b. Lifting: the strength lifting rope (belt) can bear should be 4 times the weight of the unit. Check the lifting
hook and ensure that it is firmly attached to the unit, and the lifting angle should be more than 60º. To avoid
damages to the unit, the contact position of the unit and lifting rope should be provided with an at least
50mm thick wood block, cloth or hard paper. Any person is not allowed to stand below the unit when lifting it.
25/30kW module