MCAC-ATSM-2013-11 Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz)
97
14) Ambient temperature sensor malfunction
Ambient
temperature
sensor
malfunction.
Inform the customer service
center.
PCB mistakes to alarm.
The
circuit
of
ambient
temperature sensor is broken.
Replace PCB.
Replace temperature sensor.
The
circuit
of
ambient
temperature sensor is shorten.
Replace temperature sensor.
The joint of ambient temperature
sensor is loose.
Fixed joint.
No
Yes
Yes
Yes
Yes
Yes
No
No
No