Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz) MCAC-ATSM-2013-11
92
4) Inlet &outlet water temperature difference protection
5) Low ambient temperature starting up protection
6) Low temperature anti-freezing protection of cooling evaporator
Inlet &outlet water temperature
difference protection.
Low temperature anti-freezing
protection
of
cooling
evaporator.
Inform the customer service
center.
Yes
Replace PCB.
Replace
temperature
sensor.
Refer to the water flow
malfunction to analysis.
Yes
Yes
Yes
No
No
No
Water flow is lower.
The outlet water temperature
sensor
or
inlet
water
temperature
sensor
brought
drifting
when
collect
PCB mistakes to alarm.
Replace
temperature
sensor.
Replace PCB.
Inform the customer service
center.
PCB mistakes to alarm.
Yes
Yes
Yes
Yes
No
No
Water flow is slow.
Yes
Refer to the water flow
malfunction to analysis.
Replace
temperature
sensor.
Replace PCB.
Anti-freezing temperature sensor
of cooling evaporator brought
drifting when collect temperature
Yes
PCB mistakes to alarm.
Inform the customer service
center.
No
No
No
Low ambient temperature starting
protection in cooling mode.
Yes
Ambient temperature sensor
brought drifting when collect
temperature value.