MCAC-ATSM-201606 Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
110
not be affected.
5
Shell-tube low-temperature ant-freeze sensor (Fault code Eb). Adjustment range of constant speed capability: ON and OFF.
Adjustment range of constant speed capability: ON and OFF.
6
Unit outlet water temperature sensor (Fault code E4).
Under refrigeration mode and heating mode, conduct adjustment according to the magnitude of unit outlet water
temperature.
Adjustment range of constant speed capability: ON and OFF.
7
Inlet water temperature sensor (Fault code EF).
8
Total outlet water temperature sensor (Fault code E3).
Only the main unit is valid, and the subordinate units are invalid.
Under refrigerating mode and heating mode, conduct adjustment according to the magnitude of total outlet water
temperature. Adjustment range: Load, stabilize, unload, Emergency Stop.
9
Remote mode control port(ON/OFF signal, effect on NO.0 unit).
1.Dial the code S7 in the main control board to the
“
ON
”
position and enter to the remote control mode (the wired controller
is invalid).
2.First, the ON/OFF port is closed, second, if this port is closed, the unit enters the heating mode, else, the unit enters the
cooling mode.
10
Remote control port(ON/OFF signal, effect on NO.0 unit).
1) Dial the code S7 in the main control
board to the “ON” position and enter to the remote control mode (The wired controller
is invalid).
2) If the port is closed, the unit is turned on, else, the unit is turned off.
11
Electronic expansion valve of system B.
12
Numerical code tube.
1) In case of stand-by, the address of the module is displayed.
2) In case of normal operation, 10 is displayed (10 is followed by dot).
3) In case of fault or protection, fault code or protection code is displayed.
13
Electronic expansion valve of system A.
Electronic expansion valve is used to control refrigerant flow under different operating modes and different loads.
14
Spot check. The operating status of outdoor system can be observed through spot check, and specific display contents are
as shown in the following figure:
Normal display
Operating mode
Operating capability of the compressor B
Number of online units
Outdoor ambient temp. Temp. of the condenser A
T61 frost-proof temp
Unit outlet water temp
Unit outlet-water tempe
Temp. of the condenser B
EXV opening A
EXV opening B
Operating current of system A
Operating current of system B
The last failure
●
Display contents of
“
operating mode
”
: 1. cooling; 2. heating; 4. pump; 8. Stand-by.
●
Display contents of
“
number of online units
”
: the main unit can display the number of online units, and the subordinate
unit displays 0.
15
High-pressure protection in system A and discharge temperature switch protection (Protection code P0).
High-pressure protection in system B and discharge temperature switch protection (Protection code P2).
Low-pressure protection in system A (Protection code P1).
Low-pressure protection in system B (Protection code P3).
Constant speed compressor: connection of discharge temperature switch and high-pressure switch of the system in series.
16
Power phase detection(Fault code E8)
17
Water flow detection (Fault code of the main unit E9) is only valid for the main unit but invalid for subordinate units.
Summary of Contents for Aqua Tempo Super MC-SP25-RN1L
Page 27: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 25 MC SS65 RN1L...
Page 28: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 26 MC SS80 RN1L...
Page 29: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 27 MC SS130 RN1L...
Page 31: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 29 MC SP25M RN1L...
Page 32: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 30 MC SP35 RN1L...
Page 33: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 31 MC SP35M RN1L...
Page 34: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 32 MC SP65 RN1L...
Page 38: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 36 MC SP65 RN1L...
Page 60: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 58 MC SS65 RN1L...
Page 62: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 60 MC SS65 RN1L...
Page 64: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 62 MC SS80 RN1L...
Page 70: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 68 MC SP25M RN1L...