Aqua Tempo Super Series air cooled scroll chiller unit (50Hz) MCAC-ATSM-201606
145
nvoSystem
Mode
nvoOutTemp
SNVT_count
SNVT_count
SNVT_count
SNVT_count
Details of
on-line
unit module
Setting the
min. value
of total water
outlet under
Cool mode
Setting the
min. value
of total water
outlet under
Heat mode
Setting the
max. value
of total water
outlet under
Cool mode
Setting the
max. value
of total water
outlet under
Heat mode
It could have different values if the
Air-cooled Modular units
’ model is
different.
It could have different values if the
Air-cooled Modular units
’ model is
different.
It could have different values if the
Air-cooled Modular units
’ model is
different.
It could have different values if the
Air-cooled Modular units
’ model is
different.
Display the running mode
of Air-cooled Modular
system.
The initial value of first
power on is HVAC_AUTO
Display the on-line state
of unit module If No.0 unit
module off-line, all bit of
this network variable will
change to be 0 after 1 min.
Under setting cool mode
of Air-cooled Modular
system, setting the min.
value of the total water
outlet temperature
* This network variable
only is effective when the
nciType being set as 0.
otherwise this network
variable is invalid value.
Under setting heat mode
of Air-cooled Modular
system, setting the min.
value of the total water
outlet temperature
* This network variable
only is effective when the
nciType being set as 0.
otherwise this network
variable is invalid value.
SNVT_hvac_mode
SNVT_temp_p
HVAC_COOL: Cool Mode
HVAC_HEAT: Heat Mode
HVAC_FAN_ONLY: Water pump Mode
HVAC_OFF:Off Mode
Setting water
outlet
temperature
Detail data refers to the nviSetTemp
in the input variable of Air-cooled
Modular system
NO
Name
Running
state
Network
variable name
Network
variable type
Date definition
Descriptions
1
2
5
7
8
9
6
Display the total water
outlet temperature of
Air-cooled Modular
sytem.
nvoOnNum
SNVT_count
0~16
Qty. of
on-line
units
Display the qty. of on-line
module unit of Air-cooled
Modular units.
3
nvoRunNum
nvoComState
nvoCool
TempLo
nvoHeat
TempLo
nvoCool
TempHi
nvoHeat
TempHi
SNVT_count
SNVT_state
0~16
0: Off-line
1: On-line
Qty. of
operating
unit module
Display the qty. of
operating module unit of
Air-cooled Modular units.
4
Under setting cool mode
of Air-cooled Modular
system, setting the max.
value of the total water
outlet temperature
* This network variable
only is effective when the
nciType being set as 0.
Otherwise,this variable is
invalid value.
Under setting heat mode
of Air-cooled Modular
system, setting the max.
value of the total water
outlet temperature
* This network variable
only is effective when the
nciType being set as 0.
Otherwise,this variable is
invalid value.
Summary of Contents for Aqua Tempo Super MC-SP25-RN1L
Page 27: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 25 MC SS65 RN1L...
Page 28: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 26 MC SS80 RN1L...
Page 29: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 27 MC SS130 RN1L...
Page 31: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 29 MC SP25M RN1L...
Page 32: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 30 MC SP35 RN1L...
Page 33: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 31 MC SP35M RN1L...
Page 34: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 32 MC SP65 RN1L...
Page 38: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 36 MC SP65 RN1L...
Page 60: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 58 MC SS65 RN1L...
Page 62: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 60 MC SS65 RN1L...
Page 64: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 62 MC SS80 RN1L...
Page 70: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 68 MC SP25M RN1L...