MCAC-ATSM-201606 Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
146
The network variable which is assigned to each unit module: 6 output network variable, used for
displaying detail parameters of unit modules.
bit0 : E0
bit1 : E1
bit2 : E2
bit3 : E3
bit4 : E4
bit5 : E5
bit6 : E6
bit7 : E7
bit8 : E8
bit9 : E9
bit10: EA
bit11: EB
bit12: EC
bit13: ED
bit14:EE
bit15:EF
bit0 : P0
bit1 : P1
bit2 : P2
bit3 : P3
bit4 : P4
bit5 : P5
bit6 : P6
bit7 : P7
bit8 : P8
bit9 : P9
bit10: PA
bit11: PB
bit12: PC
bit13: PD
bit14: PE
bit15: PF
nvoTemp[n]
UNVT_md
nvoOutTempS
nvoTempBackS
nvoPreFrostTemp
nvoT3A
Condenser temp T3A
nvoT3B
nvoT4
Condenser temp T3B
Error code
Unit
module
Protection code of unit
module
* n means the address
of the unit module,
nvoProtectCode [1] means
the protection code of unit
which address is 1
.
* n means the address
of the unit,
nvoTemp [1] means
the temperature paramete-
rs of unit which
address is 1.
Water outlet
temperature
of unit
Water inlet
temperature of unit.
This
variable is only
effective when the
nciType being set
as 0.
Anti-Freezing
temperature of unit.
This variable is only
effective when the
nciType being set
as 0.
Outdoor
temperature T4.
This variable is
only effective when
the nciType being
set as 0.
Each temperature
parameters of unit.
*There are 6 temperature
paremeters in nvoTemp[n].
All the temeperature type
is signed long.
Protection
code
Operating mode of unit
* n means the address of
the unit,
nvoRunMode S[1] means
the running mode of unit
which address is 1.
SNVT_hvac_mode
SNVT_lev_disc
SNVT_temp_p
HVAC_COOL:
Cool Mode
HVAC_HEAT:
Heat Mode
HVAC_FAN_ONLY: Water pump Mode
HVAC_OFF:Off Mode
NO
Name
Running
mode
Network
variable name
Network
variable type
Date definition
Descriptions
1
3
4
2
nvoErrorCod
e[n]
nvoRunMode
s[n]
nvoProtectCo
de[n]
Error code of unit
* n means the address
of the unit, nvoErrorCode
[1] means the error code
of unit which address is 1.
Summary of Contents for Aqua Tempo Super MC-SP25-RN1L
Page 27: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 25 MC SS65 RN1L...
Page 28: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 26 MC SS80 RN1L...
Page 29: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 27 MC SS130 RN1L...
Page 31: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 29 MC SP25M RN1L...
Page 32: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 30 MC SP35 RN1L...
Page 33: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 31 MC SP35M RN1L...
Page 34: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 32 MC SP65 RN1L...
Page 38: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 36 MC SP65 RN1L...
Page 60: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 58 MC SS65 RN1L...
Page 62: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 60 MC SS65 RN1L...
Page 64: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 62 MC SS80 RN1L...
Page 70: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 68 MC SP25M RN1L...