MCAC-ATSM-201606 Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
114
Under refrigeration mode and heating mode, conduct adjustment according to the magnitude of unit outlet water
temperature.
Adjustment range of constant speed capability: ON and OFF.
6
Total outlet water temperature sensor (Fault code E3).
Only the main unit is valid, and the subordinate units are invalid.
Under refrigerating mode and heating mode, conduct adjustment according to the magnitude of total outlet water
temperature. Adjustment range: Load, stabilize, unload, Emergency Stop.
7
Spot check. The operating status of outdoor system can be observed through spot check, and specific display contents are
as shown in the following figure:
Normal display
Operating mode
Operating capability of the compressor B
Number of online units
Outdoor ambient temp. Temp. of the condenser A
T61 frost-proof temp
Unit outlet water temp
Unit outlet-water tempe
Temp. of the condenser B
EXV opening A
EXV opening B
Operating current of system A
Operating current of system B
The last failure
●
Display contents of
“
operating mode
”
: 1. cooling; 2. heating; 4. pump; 8. Stand-by.
●
Display contents of
“
number of online units
”
: the main unit can display the number of online units, and the subordinate
unit displays 0.
8
Factory setting
9
8
9
A
B
C
D
E
F
8
7
6
5
4
3
2
1
0
0 1
2
3
4
5
6
7
8
F
E
D
C
B
A
9
8
ADDRRSS
Each scroll part of scroll unit has the same electric control function, and the main unit and subordinate units can be set
through address code on the electric control board. The address code 0 # is provided as the main unit. The priority of being
the main unit is given to the unit with digital compressor, and other addresses are subordinate units. Only the unit is chosen
as the main unit, its electric control can activate such functions as direct communication with the wired controller, refrigerating
and heating capability adjustment, pump control, auxiliary electric heater control, total effluent temperature detection and
water flow switch detection.
10
COM (O) 485 communication port (Fault code E2)
When the address is 0, it serves as the main
unit.
When the address is 1,2,3……F, it serves as
the subordinate unit 1,2,3……15.
Summary of Contents for Aqua Tempo Super MC-SP25-RN1L
Page 27: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 25 MC SS65 RN1L...
Page 28: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 26 MC SS80 RN1L...
Page 29: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 27 MC SS130 RN1L...
Page 31: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 29 MC SP25M RN1L...
Page 32: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 30 MC SP35 RN1L...
Page 33: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 31 MC SP35M RN1L...
Page 34: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 32 MC SP65 RN1L...
Page 38: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 36 MC SP65 RN1L...
Page 60: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 58 MC SS65 RN1L...
Page 62: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 60 MC SS65 RN1L...
Page 64: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 62 MC SS80 RN1L...
Page 70: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 68 MC SP25M RN1L...