12.2 Troubles and Solutions
Troubles
Possible reasons
Solutions
Over high air discharge
pressure (Cooling
operation).
Air or other non-condensing gas still in the system.
Discharge gas from refrigerant charging inlet.
Re-vacuum the system if necessary.
Fins in the condenser are dirty or foreign substance
blocking fins.
Clean condenser fins.
Insufficient chilling air volume or condenser fan
error.
Check and repair the condenser fan, recover the
normal operation.
Excessive high air suction pressure.
Clean the heat exchanger.
Replace the EXV, capillary, filter.
Excessive refrigerant charging volume.
Discharge the excessive refrigerant.
Over high ambient temperature
Check ambient temperature
Over low air discharge
pressure(Cooling
operation).
Surrounding temperature is lower.
Measure the surrounding Temperature
Refrigerant leak or insufficient.
Leak-hunting or recharging.
Low suction pressure.
Refer to the “low suction pressure”
Over high air
suction pressure
(Cooling operation)
Refrigerant over-charged.
Discharge the additional refrigerant.
High temperature of the inlet chilled-water.
Check the heat insulation of water pipeline.
Over low air suction
pressure (Cooling
operation).
Insufficient water flow.
Measure the temperature difference between inlet
/outlet water, adjust the water flow.
Low temperature of inlet chilled-water.
Check installation.
Refrigerant leak or insufficient.
Leak-hunting or recharging.
Scaling in the evaporator.
Descaling.
Over high air discharge
pressure (Heating
operation).
Insufficient water flow.
Check temperature difference between water inlet
and outlet, and adjust the water flow volume.
Air or other non-condensing gas still in the system.
Discharge gas from refrigerant charging inlet.
Re-vacuum the system if necessary.
Scaling in water side of heat exchanger.
Descaling.
Over high temperature in chilling water inlet.
Check water temperature
Over low air discharge
pressure (Heating
operation).
Over low temperature of chilling water.
Check chilling water temperature
Refrigerant leakage or insufficient
refrigerant volume.
Test leakage or charge sufficient refrigerant to the
system.
Excessive low air suction pressure
Add refrigerant.
Check the EXV, capillary, filter or pressure
controller.
Over high air suction
pressure (Heating
operation)
Over heat air in the side of air heat exchanger
Check ambient temperature around it.
Excessive refrigerant charging volume.
Discharge the excessive refrigerant.
Over low air suction
pressure (Heating
operation).
Insufficient refrigerant charging volume.
Charge sufficient refrigerant to the system
Insufficient air flow volume.
Check fan rotating direction
Air loop short circuit.
Reason about remove air short-circuit
Insufficient frost-removal operation.
Error comes out from 4-way valve or thermal
resistor. Replace a new one if necessary.
Compressor stops
because of
anti-freezing
protection (Cooling
operation).
Insufficient chilling water flow volume.
Error comes from pump or flow-type water volume
control. Check and repair or replace a new one.
Gas still in water loop.
Discharge air.
Thermal resistor error.
Upon error have been confirmed, please replace a
new one.
Compressor stops
because of high
pressure protection.
Over high air discharging pressure.
Discharge part of refrigerant.
Clean the heat exchanger.
Check the EXV,capillary, filter.
High pressure switch error.
Upon error have been confirmed, please replace a
new one.
Compressor stops
because of motor
overload.
Over high air discharging pressure and air suction
pressure.
Clean the heat exchanger.
Check the EXV,capillary, filter.
High voltage or low voltage, signal phase or phase
unbalance.
Confirm voltage not higher or lower than the rated
v/-10%.
Summary of Contents for Aqua Tempo Super MC-SP25-RN1L
Page 27: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 25 MC SS65 RN1L...
Page 28: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 26 MC SS80 RN1L...
Page 29: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 27 MC SS130 RN1L...
Page 31: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 29 MC SP25M RN1L...
Page 32: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 30 MC SP35 RN1L...
Page 33: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 31 MC SP35M RN1L...
Page 34: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 32 MC SP65 RN1L...
Page 38: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 36 MC SP65 RN1L...
Page 60: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 58 MC SS65 RN1L...
Page 62: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 60 MC SS65 RN1L...
Page 64: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 62 MC SS80 RN1L...
Page 70: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 68 MC SP25M RN1L...