33
8.3 Main Protection
8.3.1 Three Minutes Delay at restart for compressor
1 minute delay for the 1
st
time start-up and 3 minutes delay for others.
8.3.2 Temperature protection of compressor top
The unit will stop working when the compressor top temp. protector cut off, and will restart after the
compressor top temp. protector restart.
8.3.3 Temperature protection of compressor discharge
When the compressor discharge temp. is getting higher, the running frequency will be limited as below
rules:
---Compressor discharge temp. T5>115
℃
for 5s, compressor stops.
---108<T5<115
℃
, decrease the frequency to the lower level every 3 minutes.
---90<T5<105
℃
, keep running at the current frequency.
----T5<90
℃
, no limit for frequency.
8.3.4 Fan Speed is out of control
When Indoor Fan Speed keeps too low (300RPM) for certain time, the unit will stop and the LED will
display the failure
8.3.5 Inverter module Protection
The Inverter module has a protection function about current, voltage and temperature. If these
protections happen, the corresponding code will display on indoor unit and the unit will stop working.
8.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
8.3.7 Compressor preheating functions
Preheating permitting condition:
If T4(outdoor ambient temperature)
<
3
℃
and the machine connects to power supply newly or if T4
<
3
℃
and compressor has stopped for over 3 hours, the compressor heating cable will work.
Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of the compressor, then the
compressor is heated without operation.
Preheating release condition:
Summary of Contents for 11DSNA-A-1301
Page 1: ...NEOLA INVERTER SERIES Service Manual 2013 11DSNA A 1301...
Page 18: ...16 MS11D 22CRDN1 MN10W MS11D 22HRDN1 MN10W...
Page 20: ...18 MOC 18CDN1 MN10W MOC 18HDN1 MN5W...
Page 21: ...19 MOF 22CDN1 MN5W MOF 22HDN1 MN5W...
Page 52: ...50 9 2 2 Indoor outdoor unit s communication error diagnosis and solution E1...
Page 56: ...54 9 2 5 IPM malfunction or IGBT over strong current diagnosis and solution P0...
Page 57: ...55 9 2 6 Over voltage or too low voltage protection diagnosis and solution P1...
Page 58: ...56 9 2 7 High temperature protection of compressor top diagnosis and solution P2...
Page 59: ...57 9 2 8 Inverter compressor drive error diagnosis and solution P4...