6.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
MS11D-09HRDN1-MN5W+MOA-09HDN1-MN5W
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
8
20
20
MS11D-09CRDN1-MN5W+
MOA-09CDN1-MN5W
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
8
20
20
MS11D-09CRDN1-BN10W+MOR-09CDN1-BN10W
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
8
20
20
MS11D-09HRDN1-BN10W+MOR-09HDN1-BN10W
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
8
20
20
MS11D-12CRDN1-BN10W+MOR-12CDN1-BN10W
1/2’’
(Ф12.7)
1/4’’
(Ф6.35)
5
8
20
20
MS11D-12HRDN1-BN10W+MOR-12HDN1-BN10W
1/2’’
(Ф12.7)
1/4’’
(Ф6.35)
5
8
20
20
MS11D-12CRDN1-MN10W+MOB-12CDN1-MN10W
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
8
20
20
MS11D-12HRDN1-MN10W+MOB-12HDN1-MN10W
MS11D-18CRDN1-MN10W+MOC-18CDN1-MN10W
1/2’’
(Ф12.7)
1/4’’
(Ф6.35)
10
25
MS11D-18HRDN1-MN10W+MOC-18HDN1-MN5W
MS11D-22CRDN1-MN10W+MOF-22CDN1-MN5W
5/8’’
(Ф15.9)
3/8’’
(Ф9.52)
5
10
25
40
MS11D-22HRDN1-MN10W+MOF-22HDN1-MN5W
Caution:
The capacity test is based on standard length and maximum allowance length is based on the system
reliability.
The oil trap should be installed per 5-7 meters.
Summary of Contents for 11DSNA-A-1301
Page 1: ...NEOLA INVERTER SERIES Service Manual 2013 11DSNA A 1301...
Page 18: ...16 MS11D 22CRDN1 MN10W MS11D 22HRDN1 MN10W...
Page 20: ...18 MOC 18CDN1 MN10W MOC 18HDN1 MN5W...
Page 21: ...19 MOF 22CDN1 MN5W MOF 22HDN1 MN5W...
Page 52: ...50 9 2 2 Indoor outdoor unit s communication error diagnosis and solution E1...
Page 56: ...54 9 2 5 IPM malfunction or IGBT over strong current diagnosis and solution P0...
Page 57: ...55 9 2 6 Over voltage or too low voltage protection diagnosis and solution P1...
Page 58: ...56 9 2 7 High temperature protection of compressor top diagnosis and solution P2...
Page 59: ...57 9 2 8 Inverter compressor drive error diagnosis and solution P4...