36
F: Keep the current frequency.
G: Decrease the frequency to the lower level until to F1.
H: Run at F1 for 1h.(if T1-Ts<-2
℃
, the compressor will stop)
Meanwhile, the compressor running frequency is limited by the current.
I3COOL
I2COOL
Off
Decrease
Hold
Resume
I1COOL
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
Note:
When AC is in “hold” zone for 3 minutes, the compressor frequency will rise to the higher
level.(frequency will increase twice at most)
8.4.2.2 Outdoor fan running rules
22
20
High
Low
8.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and
auto.
Auto fan in cooling mode acts as follow: