23
the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If
the pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage
points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump.
Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum
pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas
coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is
a little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
2. Air purging by refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on
the 2-way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage.
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Summary of Contents for 11DSNA-A-1301
Page 1: ...NEOLA INVERTER SERIES Service Manual 2013 11DSNA A 1301...
Page 18: ...16 MS11D 22CRDN1 MN10W MS11D 22HRDN1 MN10W...
Page 20: ...18 MOC 18CDN1 MN10W MOC 18HDN1 MN5W...
Page 21: ...19 MOF 22CDN1 MN5W MOF 22HDN1 MN5W...
Page 52: ...50 9 2 2 Indoor outdoor unit s communication error diagnosis and solution E1...
Page 56: ...54 9 2 5 IPM malfunction or IGBT over strong current diagnosis and solution P0...
Page 57: ...55 9 2 6 Over voltage or too low voltage protection diagnosis and solution P1...
Page 58: ...56 9 2 7 High temperature protection of compressor top diagnosis and solution P2...
Page 59: ...57 9 2 8 Inverter compressor drive error diagnosis and solution P4...