8.4.5.3 Low indoor room temperature protection
In drying mode, if room temperature is lower than 10
℃
, the compressor will stop and not resume until
room temperature exceeds 12
℃
.
8.4.5.4 Evaporator anti-freezing protection, condenser high temperature protection and outdoor unit
frequency limit are active and the same as that in cooling mode.
8.4.5.5 The outdoor fan operates the same as in cooling mode.
8.4.6 Forced operation function
8.4.6.1 Enter forced operation function:
When the machine is off, pressing the touch button will carry the machine to forced auto mode. If
pressing the button once again within 5 seconds, the machine will turn into forced cooling mode.
In forced auto, forced cooling or any other operation mode, pressing touch button will turn off the
machine.
8.4.6.2 In forced operation mode, all general protections and remote control are available.
8.4.6.3 Operation rules:
Forced cooling mode:
The compressor runs at F2 frequency and indoor fan runs as breeze. After running for 30 minutes. the
machine will turn to auto mode as 24
℃
setting temperature.
Forced auto mode:
The action of forced auto mode is the same as normal auto mode with 24
℃
setting temperature.
8.4.7 Timer function
8.4.7.1 Timing range is 24 hours.
8.4.7.2 Timer on. The machine will turn on automatically when reaching the setting time.
Summary of Contents for 11DSNA-A-1301
Page 1: ...NEOLA INVERTER SERIES Service Manual 2013 11DSNA A 1301...
Page 18: ...16 MS11D 22CRDN1 MN10W MS11D 22HRDN1 MN10W...
Page 20: ...18 MOC 18CDN1 MN10W MOC 18HDN1 MN5W...
Page 21: ...19 MOF 22CDN1 MN5W MOF 22HDN1 MN5W...
Page 52: ...50 9 2 2 Indoor outdoor unit s communication error diagnosis and solution E1...
Page 56: ...54 9 2 5 IPM malfunction or IGBT over strong current diagnosis and solution P0...
Page 57: ...55 9 2 6 Over voltage or too low voltage protection diagnosis and solution P1...
Page 58: ...56 9 2 7 High temperature protection of compressor top diagnosis and solution P2...
Page 59: ...57 9 2 8 Inverter compressor drive error diagnosis and solution P4...