Type OTN2 / OTD2 with room or floor sensor                                  English

Pollution class: 2

Pollution class 2, representative of air circulation in typical homes. 

Overvoltage category: III

Pulse voltage 4 kV to IEC 60664-1.

Sensor installation

Floor sensor:
The floor sensor should be installed in standard conduit embedded 
in the floor. The conduit should be sealed and positioned as close 
to the floor surface as possible. 

Room sensor:
The room sensor should be installed in a standard wall box or 
mounted direct on the wall. Sensor cables can be extended up to a 
maximum of 50 m in length using power cable. Two wires in a multi-
wire cable must, however, not be used if the cable is also used to 
supply power to heating cables. The best result is achieved if a se-
parate cable, installed in a separate conduit, is used for the sensor.

Installation of thermostat 

Built-in or external room sensor
The thermostat or external room sensor should be mounted on a 
wall in such a way as to allow free air circulation around it. It must 
also be positioned so as to prevent it from being affected by direct 
heat sources (e.g. the sun), draughts from doors and windows, or 
outside temperature (i.e. do not mount on outer walls). MICRO-
LINE has a built in fault circuit which switches the heating off if the 
sensor is disconnected or short-circuited.

Thermostat installation
-   Open cover.
-   Unscrew cover and remove. 
-   Connect wires from rear as shown in wiring diagram.
-   Mount thermostat in wall box - fit frame and cover.

Temperature setting

Interrupter

LED

Increase temperature

Programming button (P)

Decrease temperature

MICROLINE has a temperature setting range of 0-40°C.
Set the wanted temperature with the arrow buttons, the set  tempe-
rature shows in the display.  The thermostat will calculate the best 
way to control the heating system in order to achieve the desired 
temperature. If necessary, fine adjustment can be performed after 
1 or 2 days. 

Night setback

The night setback/economy temperature function is activated via 
a 230 V signal from an external timer connected to terminal S.
The function is factory set to 5°C (2-8° OTD2). The LED lights green 
when the economy signal is active and red when heating is active.

Frost protection

If the signal is connected via a rectifier diode, the thermostat will 
maintain a floor/room temperature of 5°C.

Settings

To set parameter values, press and hold the programming button 
for 3 seconds. SCA 

 Hi 

 40 will be shown on the display. First-

ly, SCA will be displayed for 1 second, followed by Hi, and finally 
40. The required value can then be set using the arrow buttons. To 
access the next parameter, press the programming button again. 
If no buttons are pressed for 30 seconds, the program returns to 
the initial display.

Parameter

Shown on display

Factory setting 
OJ standard

OTD2 -1999

OTN2 -1991

OTN2 -1999

Max. temperature

SCA   

   Hi   

   40

40°C (0-40°C)

Min. temperature

SCA   

   Lo   

   0

0°C (0-40°C)

Max. limit temperature  FLOOR

Li   

   Hi     

   28

28°C (15-55°C)

Min. limit temperature   FLOOR

Li   

   Lo   

   15

15°C (5-30°C)

Measure floor temperature

FLo   

   24.5

Measured room temperature

ro   

   21.5

Application

APp   

   A : Room sensor   *1

 F : Floor sensor   *2

 AF : Room with Limit sensor   *2

 C : Controller

Offset

oFF 

    

0   0   (+/- 3°C) 

Night setback/ECO

nSb 

5   5°C (2-8°C)

*1 : Only available if floor sensor is not installed
*2 : Only available if floor sensor is installed

If Controller (C) is selected under Application, the floor and room sensors are disconnected and heating is controlled on a scale of 0-10, 
corresponding to 0-100% activated

Error codes

E1

 -  Sensor error. Sensor is short-circuited or disconnected. The LED is flashing red once.

E2

 -  Limit error. The temperature on the floor has surpassed max. limit temperature. The thermostat switch off the heating and the LED is 

 

  flashing red twice.  

E5

 -  Overheating. The temperature is too high in the termostat and switch off the heating. The LED is flashing 5 times. 

Summary of Contents for OTD2-1999

Page 1: ...d checked by authorised personnel before being connected to the power supply The product carries a manufacturer s warranty if installed in accor dance with these instructions and applicable regulation...

Page 2: ...to achieve the desired temperature If necessary fine adjustment can be performed after 1 or 2 days Night setback The night setback economy temperature function is activated via a 230 V signal from an...

Page 3: ...mbol must not be dis posed of together with household refuse but must be delivered to a waste collection centre in accordance with current local regulations Type UCG UDG English OJ Electronics A S Ste...

Page 4: ...rsorgung von autorisiertem Personal begutachtet und gepr ft werden F r dieses Produkt wird vom Hersteller Garantie gew hrleistet wenn es gem dieser Anleitung und den anwendbaren Richtlinien installier...

Page 5: ...zu erreichen Falls erforderlich nach 1 bis 2 Tagen eine Feinjustierung vornehmen Nachtabsenkung Die Nachtabsenkungs Spartemperatur Funktion wird ber ein an die Klemme S angeschlossenes 230 V Signal vo...

Page 6: ...nicht gemeinsam mit Haushaltsabfall entsorgt werden sondern m ssen entsprechend den lokalen Richtlinien bei einer Abfallsammelstelle abgeliefert werden Typ OTN2 OTD2 mit Raum oder Bodenf hler Deutsch...

Page 7: ...NI 10 Microline OTN2 1991 OTN2 1999 OTD2 1999 CE EN 61000 6 3 EN 61000 6 2 EN 60 730 1 EN 60730 2 9 230 15 50 16 2 16 SPST NO 16 3600 0 40 0 4 5 2 8 OTD2 230 5 230 20 0 40 84 84 40 IP21 II 1 L1 230 15...

Page 8: ...8 2009 OJ Electronics A S OTN2 OTD2 III 4 IEC 60664 1 50 MICROLINE P MICRO LINE 0 40 C 1 2 230 5 5 2 8 OTD2 5 3 SCA Hi 40 SCA 1 Hi 40 30...

Page 9: ...4 Fax 45 73 12 13 13 oj oj dk www oj dk 10 0 10 20 30 64000 38000 23300 14800 9700 BR929A08 rus OJ OTD2 1999 OTN2 1991 OTN2 1999 SCA Hi 40 40 C 0 40 C SCA Lo 0 0 C 0 40 C Li Hi 28 28 C 15 55 C Li Lo 1...

Page 10: ...je eli instalacja zosta a przeprowadzona zgodnie z powy szymi zaleceniami i aktu alnymi przepisami Dane techniczne Zasilanie 230 V AC 15 50 Hz Maksymalne zabezpieczenie 16 A Wbudowany wy cznik 2 polow...

Page 11: ...e ustawienie temperatury mo e zaj 1 2 dni Nocne obni enie temperatury Funkcja nocnego obni enia temperatury ekonomicznej aktywowana jest poprzez sygna kontrolny 230V pochodz cy z zewn trznego zegara p...

Page 12: ...naturalne poprzez w a ciw utylizacj opakowa i zu ytych produkt w Utylizacja produkt w Produkty oznaczone tym znakiem nie mog by wyr zucane wsp lnie z odpadkami domowymi Konieczne jest dostarczenie ic...

Page 13: ...OTN2 1991 OTN2 1999 OTD2 1999 EN 61000 6 3 EN 61000 6 2 EN 60 730 1 EN 60730 2 9 230 15 50 16 A 2 16 SPST NO 16 A 3600 0 40 C 0 4 C 5 C 2 8 C OTD2 230 5 C 230 20 C 0 40 C 84 84 40 IP 21 II 1 L1 230 1...

Page 14: ...NE 0 40 C 230 5 5 C 2 8 OTD2 5 C 3 SCA Hi 40 1 SCA Hi 40 30 OJ OTD2 1999 OTN2 1991 OTN2 1999 SCA Hi 40 40 C 0 40 C SCA Lo 0 0 C 0 40 C Li Hi 28 28 C 15 55 C Li Lo 15 15 C 5 30 C FLo 24 5 ro 21 5 APp A...

Page 15: ...ctronics A S OJ Electronics A S Stenager 13B DK 6400 S nderborg 45 73 12 13 14 45 73 12 13 13 oj oj dk www oj dk 10 0 10 20 30 64000 38000 23300 14800 9700 Valor ohmios Sensor Temp C BR929A08 E E1 E2...

Page 16: ...Electronics A S The OJ trademark is a registred trademark belonging to OJ Electronics A S OJ ELECTRONICS A S Stenager 13B DK 6400 S nderborg Tel 45 73 12 13 14 Fax 45 73 12 13 13 oj oj dk www oj dk 5...

Reviews: