RFT9709 Transmitter Instruction Manual
43
RFT9709 Specifications
continued
Hazardous area approvals
When properly installed with an approved sensor, the RFT9709
transmitter can be installed in the following areas:
UL
Class I, Div. 2, Groups A, B, C, and D. Provides nonincendive sensor
outputs for use in Class I, Div. 2, Groups A, B, C, and D; or intrinsically
safe sensor outputs for use in Class I, Groups C and D, and Class II,
Groups E, F, and G.
UL Division 2 nonincendive parameters
CSA
Approval pending
Weight
Standard housing
1.5 lb (0.68 kg)
Housed in factory-supplied NEMA-4 (IP65) enclosure 6.5 lb (2.9 kg)
Parameter
Analog output
(Terminals 11-12, 13-14)
Frequency/pulse output
(Terminals 17-18)
V
OC
36.5 V
16 V
I
SC
22 mA
51 mA
C
a
0.135 µf
1.5 µf
L
a
100 mH
37 mH