Lo-Rider Designer Vent Free Fireboxes
ClearanCes and heiGht requirements
Ensure that minimum clearances shown in
Figures 3 through 7
are maintained. left and right clear-
ances are determined when facing the front of the firebox.
Follow these instructions carefully to ensure safe installation. Failure to follow these requirements
may create a fire hazard.
1.
sidewall Clearances
— The clearance from the inside of the appliance to any combustible
adjacent wall should not be less than 5
B\,
".
Refer to Figure 3.
2.
Ceiling Clearance
— The ceiling must be at least 42" from the top of the firebox opening (bottom
of hood).
Refer to Figure 3.
3.
back Wall Clearance
— The appliance may be placed against a combustible back wall.
4.
parallel Wall Clearance
— The clearance from the opening of the firebox to any wall that is
parallel to the opening should not be less than 36" (lSTF36 and lPF36 models only).
Refer to
Figure 4.
Figure 3 -
Sidewall and Ceiling Clearances
42”
(1067 mm)
5
6
”
(143 mm)
FP2319
wall clng clearances
FP2319
Figure 4 -
Parallel Wall Clearance
(LSTF36 and LPF36 Models Only)
36”
(914 mm)
FP2320
wall clearance
FP2320
Figure 5 -
Hearth Dimensions
A
B
C
FP2321
hearth dims
FP2321
hearth Dimensions
A
B
C
See-thru
33
C\zn
"
21
ZB\zn
"
27
C\v
"
(843 mm) (608 mm) (705 mm)
Corner
35
B\zn
"
21
ZB\zn
"
27
C\v
"
(897 mm) (608 mm) (705 mm)
Peninsula
35
B\zn
"
21
ZB\zn
"
27
C\v
"
(897 mm) (608 mm) (705 mm)