7.4
Electrical
Power cables
Cable lengths need to be taken into account when designing a battery system. Batteries can be placed in
parallel, for example in 24 VDC systems, or in series up to 460 VDC.
NOTICE:
Use the correct cable type for the applicable system voltage.
Use the correct fuses for the applicable cable cross-section.
We recommend to size the cables to limit voltage drop to 1% or less.
NOTICE:
Check the power connections for excessive temperatures during a load test.