2.1.
Controller unit
Prozessor NXP i.MX7D Dual Core ARM
®
Cortex
®
- A7, frequency 1 GHz.
Internal storage:
- 512 MB RAM
- 4 GB Flash.
Operating system Linux embedded
RealTimeClock:
- with an accuracy of 1 s per day
- 10 hrs. Power failure bridging
2.2.
In- and outputs
The EWIO
2
and EWIO
2
-M variants are available:
8 digital inputs for recording and counting binary states up to 24 Volt DC
4 of them are galvanically isolated.
4 switchable digital 24 Volt outputs with current carrying capacity of up to 20 mA DC
per output
3 analogue inputs. Configurable for
- 0-10 Volt DC voltage measurement,
- Resistance measurement in the range from 40 Ohm to 4 Megaohm or
- Temperature measurement. 17 different sensor types can be selected.
- 0-20mA DC current measurement,
3 analog outputs with manual operation with 0-10 Volt DC with a
current carrying capacity up to 5 mA per output.
Only for EWIO
2
variants are available:
6 switchable relay outputs with manual operating up to 6 A per relay
2 switchable TRIAC outputs with manual control with 20-250 Volt AC
with a current carrying capacity of up to 0.5 A per TRIAC
Only for EWIO
2
-M variants are available:
4 switchable relay outputs with manual operating with one current carrying capacity
up to 6 A per relay