Flag 6: Evaluation of the status in the counter response. If there are no errors, the Flags is set
to I.
I = response telegram from MBus „All right“
E = Response telegram from MBus contains error status
Flag 7: The timer or the synchronous pulse triggers the reading of the measured value.
S = synchronization pulse
T = internal timer of the EWIO
2
-M
10.5.6.4.
Modbus settings (counter)
In the menu window "Modbus settings (counter)" the communication parameters baud rate
and parity for the fieldbus interface are set.
In the pop-up menus the baud rates of 1200, 2400, 4800, 9600, 19200, 38400, 57600 and
115200 bps and the parity none with 1 stop bit, none with 2 stop bits, even and odd parity
can be selected.
When Expert Mode is activated, see Chapter
General, the menu window is extended.
In the input fields "Retries (0...10)" and "Timeout Frame [ms] (0...5000)" you can select how
often a Modbus request should be sent and how long to wait for a response from a counter.