5.3.
In- and outputs (I/Os)
Various sensors and actuators can be connected to the dedicated I/Os.
Note !
Sensor cables, including shielded ones, must be laid at a sufficient distance
from live cables so that the measured values are not affected.
5.3.1.
Relay
The terminals of the respective relay outputs have the following meanings
the common connections (COM) with 11, 21, 31, 41, 51, 61,
the normally closed contacts (NC) 12, 22, 32, 42, 52, 62 and
the normally open contacts (NO) 14, 24, 34, 44, 54, 64.
They can be switched individually and can carry up to 6 A resistive load.
5.3.2.
TRIAC
(Only for the Ethernet I/O variants.)
The terminals of the respective TRIAC outputs (semiconductor outputs) are T13..T14 and
T23..T24. They can be switched individually and can be loaded up to 0.5 A.