![METREL PowerQ4MI 2592 Instruction Manual Download Page 99](http://html1.mh-extra.com/html/metrel/powerq4mi-2592/powerq4mi-2592_instruction-manual_1778984099.webp)
6 Technical specifications
99
6.3 Standards
compliance
6.3.1 Compliance to the IEC 61557-12
General and essential characteristic
Power quality assessment function
-S
SD
Indirect current and direct voltage
measurement
Classification according to 4.3
SS
Indirect current and indirect voltage
measurement
Temperature
K50
Hu altitude
Standard
Measurement characteristic
Function symbols Class according
to IEC 61557-12
Measuring range
Measuring method
IEC 61000-4-30 Class
P
1
5 % ÷ 200% I
Nom
(1)
Q
1
5 % ÷ 200% I
Nom
(1)
S
1
5 % ÷ 200% I
Nom
(1)
eP
1
5 % ÷ 200% I
Nom
(1)
eQ
2
5 % ÷ 200% I
Nom
(1)
eS
1
5 % ÷ 200% I
Nom
(1)
PF
0.5
- 1 ÷ 1
f
0.02
10 Hz ÷ 70 Hz
S
I, I
N
0.5
5 % I
Nom
÷ 200 % I
Nom
S
U
0.2
20 V ÷ 1000 V
S
P
st
,P
lt
5
0.4 ÷ 4
S
U
dip,
U
swl
0.5
5 V ÷ 1500 V
S
U
int
0.5
0 V ÷ 100 V
A
u
-
,
u
0
0.2
0.5 % ÷ 17 %
A
Uh
n
1
0 % ÷ 20 % U
Nom
S
THD
u
1
0 % ÷ 20 % U
Nom
S
Ih
n
1
0 % ÷ 100 % I
Nom
A
THD
i
2
0 % ÷ 100 % I
Nom
A
(1) - Measurement range depends on current sensor. However according to the IEC
61557-12, if current sensor has I
Nom
defined as I
Nom
=
k
· A/V, then measurement range
is: 2 % I
Nom
÷ 200 % I
Nom
.