22
• Coeffient Of Performance Test - COP
The COP test allows you to measure the energy efficiency of your system.
Following data is recorded:
- COP: Current, Min/Max, AVG
- Cooling Capacity: Current, Min/Max, AVG
- Ambient Temp.: Current, Min/Max, AVG.
For measuring the Seasonal COP
2. Select ‘COP Test’.
3. Complete the COP Test Setup.
You must assign at least 2 pressure sensors
and 3 temperature sensors. A third pressure
sensor is needed if your refrigerant has glide.
You can add Amperage sensors and a tem-
perature sensor for ambient temperature.
1. Select ‘Main Menu’ and select ‘Tests’.
4. Press ‘Start’
You get the COP Status
5. When stopping you get a .csv file and the
following report:
Main Menu
COP