16

@2019 KITA Sensor Tech. Co., LTD.                                                                                                   URL hiip://www.kita.com.tw

-15-

K F P 0 1  

Series

  Instruction Manual

How to Use

2. Pressure sensor setting

Press      or      button at Function Selection Mode to display 

[

F-01

] [

oUt1

].

Output Mode Setting

Select output mode

Press      or       button to select output
mode of OUT1.

Hysteresis Mode

Ag

kPa

L /min

Window Comparator Mode

One Point Set Mode

Ag

kPa

L /min

Ag

kPa

L /min

Ag

kPa

L /min

Press        button

Ag

kPa

L /min

Sensor Selection

Press      or       button to select 
pressure sensor of OUT1.

Flow sensor

Ag

kPa

L /min

Pressure sensor

Ag

kPa

L /min

Press        button

(to be continued)

Press        button

Selected

Output

Sensor

Selected

Mode

Sensor

Summary of Contents for FLUX 0

Page 1: ...FLUX 0 DIGITAL FLOWMETER AND PRESSURE SENSOR USER MANUAL...

Page 2: ...2...

Page 3: ...oad meets the following formula Power Supply Internal voltage Minimum operating voltage drop of sensor voltage of load Do not operate the product outside the specifications The sensor will be damaged...

Page 4: ...tighten will damage the product Do not mount the sensor in a place that will be used as a foothold The product may damage if sit or step on it accidentally When mounting without a bracket please use...

Page 5: ...range of catalog or and not following the instruction manual The sensing element cannot measure properly if foreign matter adheres to it On the inlet side be sure to install an air filter below the fi...

Page 6: ...6...

Page 7: ...rd selection PAGE 26 2 3 8 F 08 Analog output selection PAGE 27 2 3 9 F 09 Accumulated value hold selection PAGE 28 2 3 10 F 10 Flow sensor display mode selection PAGE 29 2 3 11 F 91 Power save mode s...

Page 8: ...alfunction or damage to the product Piping for the One Touch Fitting insert the tube firmly into the fitting and make sure it cannot be pulled out Also using the proper tube cutter is recommended to e...

Page 9: ...rizontally or vertically but the flow rates may change because of the installation way of the product or piping The tightening torque for screws should be under 0 5 0 1 N m 1 Horizontal mounting by Th...

Page 10: ...ite Output 2 Yellow External input Yellow External input Orange Analog output Orange Analog output 1 2 3 4 5 6 1k 1 3 Wiring Diagrams 1 3 1 PNP Output Analog Output and External Input Brown Orange Yel...

Page 11: ...ort Inlet side Output 1 Indicator 3 Color LCD Display Flow Symbol Flow Display Button Button Analog Signal Indicator Output 2 Indicator Output 1 Indicator Output 2 Indicator Analog Signal Indicator Pr...

Page 12: ...Select the flow value is shown under standard ANR or normal condition NOR Select the analog corresponding to pressure or flow sensor To save the last accumulated flow value every 2 or 5 minutes Select...

Page 13: ...o display F 01 Press or button to select other setting functions Press for 3 sec at Function Setting Mode to return to Measurement Mode 2 3 Operation Instructions Function Selection Mode Ag kPa L min...

Page 14: ...r of OUT1 Flow sensor Ag kPa L min Selected Output Sensor Pressure sensor Press button to be continued Ag kPa L min Output Mode Setting Select output mode Press or button to select output mode of OUT1...

Page 15: ...t Value Setting Out1 set value setting Press or button to adjust the set value Hysteresis Mode HYS FL 1 FH 1 Window Comparator Mode FL 1 FH 1 Accumlated Output Mode ADD AddL AddH NOTE Set value settin...

Page 16: ...ng Select output mode Press or button to select output mode of OUT1 Hysteresis Mode Ag kPa L min Window Comparator Mode One Point Set Mode Ag kPa L min Ag kPa L min Ag kPa L min Press button Ag kPa L...

Page 17: ...ust the set value Hysteresis Mode HYS L 1 H 1 Window Comparator Mode L 1 H 1 One Point Set Mode oPS P 1 Ag kPa L min Fixed Hysteresis Setting Fixed hysteresis setting Press or button to adjust fixed h...

Page 18: ...L 2 L 1 L 2 FH 1 FH 2 H 1 H 2 P 1 P 2 Time AdH1 AdL1 AdH2 AdL2 Pressure Flow NOTE 1 In case hysteresis is set at less than or equal to 2 digits switch output may chatter if input pressure fluctuates n...

Page 19: ...l How to Use 2 3 2 F 02 OUT2 Setting Selection Setting corresponding sensor and operating mode of OUT2 1 Press or button at function setting mode to start OUT 2 Setting F 02 oUt2 2 Check the F 01 for...

Page 20: ...r button to select color display for OUT1 or OUT2 Display color of OUT1 Ag kPa L min Display color of OUT2 Display Color Mode Selection Press the or button to select Display Color Mode ON Green OFF Re...

Page 21: ...onse Time Selected Sensor Ag kPa L min Ag kPa L min 2 3 4 F 04 Response Time Selection Select proper response time to avoid switch output chattering Press or button at Function Selection Mode to displ...

Page 22: ...sensor Ag kPa L min Pressure sensor Response Time Selection 2 5ms 25ms 1500ms Ag kPa L min Selected Sensor Set Value Ag kPa L min Ag kPa L min Ag kPa L min Setting response time of pressure sensor Pr...

Page 23: ...the proper display refresh time to reduce frequently changing value Press or button at Function Selection Mode to display F 05 UPdA 1 Flow sensor setting Setting refresh time of flow sensor Press or b...

Page 24: ...pressure sensor Flow sensor Pressure sensor Ag kPa L min Display Refresh Time Setting Set Value Refresh Time Ag kPa L min Setting refresh time of pressure sensor Press or button to select refresh time...

Page 25: ...10 2 Ag kPa L min Ag kPa L min Ag kPa ft3 min Pressure Unit Selection Press or button to select pressure unit Ag kPa L min Ag kPa L min Ag kgf cm2 L min Ag bar L min Ag psi L min Set Unit Pressure Se...

Page 26: ...erence Standard Selection Press or button to select the standard or normal condition Standard conditon ANR Normal condition NOR Ag kPa L min Ag kPa L min Ag kPa L min Flow Reference Selected Condition...

Page 27: ...or pressure sensor Operation Press or button at Function Selection Mode to display F 08 AnG Sensor Selection Press or button to select the sensor of analog output Flow sensor Pressure sensor Ag kPa L...

Page 28: ...he memory device is 1 million cycles If the sensor is operated 24 hours per day the durability is calculated as below 5 minutes x 1 million cycles 5 million minutes 9 5 years 2 minutes x 1 million cyc...

Page 29: ...button at Function Selection Mode to display F 10 DiS Display Mode Selection Press or button to select display mode Instantaneous Flow Mode Accumulated Flow Mode Ag kPa L min Ag kPa L min Ag L Ag kPa...

Page 30: ...ons is pressed in 30 sec press any keys to leave the Power Save Mode Operation Press or button at Function Selection Mode to display F 91 ECo Power Save Mode Selection Press or button to turn on the p...

Page 31: ...ed The switch output function operates relative to its change This function is only for output 1 corresponding to flow sensor action point When external signal is input please connect the input wire t...

Page 32: ...djust flow and pressure display values Display values can be calibrated to within 2 5 R D Press or button at Function Selection Mode to display F 94 FinE 1 Fine adjustment of instantaneous flow value...

Page 33: ...ure value Ag kPa L min Ag kPa L min Ag kPa L min Ag kPa L min Fine Adjustment of Pressure Value Fine adjustment of pressure value Press or button to setting fine adjustment of display value Ag kPa L m...

Page 34: ...Press or button to setting OUT1 OUT1 OFF OUT1 ON Ag kPa L min Ag kPa L min Ag OUT1 kPa L min Set Value Output 1 Ag kPa L min OUT2 setting Press or button to setting OUT2 OUT2 OFF OUT2 ON Ag kPa L min...

Page 35: ...y default settings can be restored Operation Press or button at Function Selection Mode to display F 99 rESt Reset to The Default Setting Press or button to return to the factory default setting Disab...

Page 36: ...ro point at the time of shipment from the factory Operation Press and button simultaneously over 3 sec at the measurement mode not Accumulated flow value display mode until display 00 And release hold...

Page 37: ...he zero point at the time of shipment from the factory Operation Press and button simultaneously over 3 sec at the measurement mode not Accumulated flow value display mode until display 00 And release...

Page 38: ...alue return to zero Operation Press and button simultaneously over 3 sec at the measurement mode Accumulated flow value mode until display zero And release holding the button to return measurement mod...

Page 39: ...when the power was supplied to this moment is detected and updated Operation Press button over 3 sec at the measurement mode The maximum value will be displayed flashing and is held Press button retu...

Page 40: ...m when the power was supplied to this moment is detected and updated Operation Press button over 3 sec at the measurement mode The minimum value will be displayed flashing and is held Press button ret...

Page 41: ...while the key lock setting is ON LoC on is displayed for 1 sec Operation Press button over 5 sec at measurement mode to select key lock unlock setting Key Lock Unlock Setting Press or button to select...

Page 42: ...no pressure conditions Reduce the flow to the display range Reduce the pressure to the display range Ensure the flow is in the correct direction Reduce the pressure to the display range Output 2 load...

Page 43: ...5 FS 1 digit Pressure Guaranteed measuring range 0 to 100 FS Display accuracy 2 FS 1 digit Analogue output accuracy 2 5 FS Repeatability 0 2 FS 1 digit Linearity 1 FS Temperature characteristic 2 FS...

Page 44: ...re Sensor 2 Temperature Sensor 1 Heating Element Temperature Sensor 2 Temperature Sensor 1 Heating Element Temperature Sensor 2 5 THERMAL MASS FLOW SENSOR PRINCIPLES FLUX 0 50 L FLUX 0 200 L ANALOGUE...

Page 45: ...CONSTRUCTION Case PC ABS Liquid crystal cover PC Electronic circuit board Port Filter Stainless Steel Resin Body PBT O ring NBR Sensor Noryl Button Silicone Liquid crystal One Touch Fitting 6 DIMENSI...

Page 46: ...46 www metalwork eu ZVAVA9007 EN IM01_07 2020 NOTES...

Reviews: