background image

* Ther mostat wires tagged “W” and “G” must be 
connected together except when using a general purpose 
"SPDT" 24VAC relay and a standard thermostat with 
subbase, or when using Honeywell T834H-1009 or 
T834H-1017 thermostats. Also refer to Figure 8 for other 
wiring connections.

Figure 8 - C1267G

THERMOSTAT HEAT ANTICIPATOR ADJUSTMENTS:
The initial heat anticipator setpoint should equal the 
thermostat's current amperage draw when the unit is 
firing. This setpoint should be measured for the best 
results. Use the recommended ranges as a guide. If 
further information is needed, consult your thermostat 
manufacturer's instructions.

Recommended Heat Anticipator Setting Ranges:

 

 

25 ft. (7.6m) 

50 ft. (15.2m)

Gas Ignition Type 

T'stat Wiring 

T'stat Wiring

For Power Vented Units: 

0.85 to 0.90 A 

0.90 to 1.1 A

Intermittent (Spark) 

 

Max. Setting 

  

 

on 

T'stat

FAN TIME DELAY CONTROL 
Leads from time delay controls are factory wired to 
the junction box. The fan control is a time delay relay 
(approximately 45 seconds ON, 65 seconds OFF). The 
fan control is rated at 17 amps.  

NOTICE: The start-up fan delay must not exceed 90 
seconds from a cold start.

IMPORTANT: For all wiring connections, refer to the 
wiring diagram that your unit is equipped with (either 
affi xed to the side jacket or enclosed in your unit's 
installation instruction envelope). Should any original 
wire supplied with the heater have to be replaced, 
it must be replaced with wiring material having a 
temperature rating of at least 105°C. 

Should any high limit switch wires have to be 
replaced, they must be replaced with wiring material 
having a temperature rating of 200°C minimum.

11

ELECTRICAL CONNECTIONS

HAZARDOUS VOLTAGE! 
disconnect ALL ELECTRIC 
POWER INCLUDING REMOTE 
DISCONNECTS BEFORE 
SERVICING. Failure to 
disconnect power before 
servicing can cause severe 
personal injury or death.

Standard units are shipped for use on 115 volt, 60 hertz 
single phase electric power. The motor name-plate and 
electrical rating on the transformer should be checked 
before energizing the unit heater electrical system. All 
external wiring must conform to the latest edition of 
the ANSI/NFPA No. 70, National Electrical Code and 
applicable local codes; in Canada, to the Canadian  
Electrical Code, Part 1 CSA Standard C22.1.

 Do not use any tools (i.e. screwdriver, 

pliers, etc.)  across the terminals to check for power.  
Use a voltmeter.

The transfor mer supplied with this unit heater is          
internally fused. Any overload or short circuit will ruin        
the transformer.

It is recommended that the electrical power supply to 
each unit heater be provided by a separate, fused and 
permanently live electrical circuit. A disconnect switch 
of suitable electrical rating for each unit heater should 
be located as close to the gas valve and controls as 
possible. Each unit heater must be electrically grounded 
in accordance with the latest edition of the National 
Electric Code, ANSI/NFPA No. 70 or CSA Standard 
C22.1.

THERMOSTAT WIRING AND LOCATION

NOTICE: The thermostat must be mounted on a 
vertical vibration-free surface free from air currents 
and in accordance with the furnished instructions.

Mount the thermostat approximately 5 feet (1.5 m) above 
the floor in an area where it will be exposed to a free 
circulation of average temperature air. Always refer to the 
thermostat instructions as well as our unit wiring diagram 
and wire accordingly. Avoid mounting the thermostat in 
the following locations:
1.  Cold areas - Outside walls or areas where drafts          

may affect the operation of the control.

2.  Hot areas - Areas where the sun's rays, radiation, or 

warm air currents may affect control operation.

3.  Dead areas - Areas where air cannot circulate freely, 

such as behind doors or in corners.

Summary of Contents for IIEB-11

Page 1: ...l operate and maintain unit in accordance with manufacturer s instructions to avoid exposure to fuel substances or substances from incomplete combustion which can cause death or serious illness The st...

Page 2: ...bled high static pressure type centrifugal blower unit designed for heavy duty applications such as continuous operation or where a single unit heater must do the entire heating job in a large area Th...

Page 3: ...ly with the general safety information may result in extensive property damage severe personal injury or death This product must be installed by a licensed plumber or gas fitter when installed within...

Page 4: ...94 1295 1295 1226 1295 1295 E Hanging Distance Width 14 1 2 17 1 4 17 1 4 20 22 3 4 25 1 2 28 1 4 33 3 4 39 1 4 44 3 4 368 438 438 508 578 648 718 857 997 1137 F Discharge Opening Width 15 3 8 18 1 8...

Page 5: ...as ignition system the unit heater must be installed such that the gas ignition control system is not directly exposed to water spray rain or dripping water NOTE Location of unit heaters is related di...

Page 6: ...r and can actually drip water down from the unit heater onto floor surface Additional unit heaters should be installed if a minimum 50 F 10 C thermostat setting cannot be maintained AIR FOR COMBUSTION...

Page 7: ...1 3 54 3 34 3 11 2 92 2 63 2 38 2 18 2 04 1 1 049 680 465 375 320 285 260 240 220 205 195 175 160 145 135 19 3 13 2 10 6 9 06 8 07 7 36 6 80 6 23 5 80 5 52 4 96 4 53 4 11 3 82 1 1 4 1 380 1400 950 770...

Page 8: ...al gas applications install a pressure regulating valve in the line upstream from the main shutoff valve 3 Adequately support the piping to prevent strain on the gas manifold and controls 4 To prevent...

Page 9: ...ER ASSEMBLY FOR THE 100 250 UNITS CONSISTS OF 1 WHEEL 1 HOUSING 1 SHAFT AND 1 BEARING SET FOR 300 400 UNITS THE BLOWER ASSEMBLY CONSISTS OF 2 WHEELS 2 HOUSINGS 1 SHAFT AND 1 BEARING SET Figure 7 Motor...

Page 10: ...ase motors require a contactor or starter if specified 4 Motor frame must not exceed NEMA frame 56 Average value all speeds and frequencies 10 327 345 362 380 397 414 431 448 466 483 500 518 535 552 5...

Page 11: ...re to disconnect power before servicing can cause severe personal injury or death Standard units are shipped for use on 115 volt 60 hertz single phase electric power The motor name plate and electrica...

Page 12: ...16 for special installation requirements regarding these venting conditions CARBON MONOXIDE Your venting system must not be blocked by any snow snow drifts or any foreign matter Inspect your venting...

Page 13: ...feet 1 2m from electric meters gas meters regulators and relief equipment Seal ALL vent pipe joints and seams to prevent leakage Use General Electric RTV 108 or Dow Corning RTV 732 silicone sealant or...

Page 14: ...14 Figure 13 Figure 14...

Page 15: ...15 Figure 15 Figure 16...

Page 16: ...fan switch delays the operation of the fan until the heater is warmed then keeps the fan running after the gas has been turned off until the useful heat has been removed The start up fan delay must no...

Page 17: ...4 BURNER SPRINGS 5 MAIN BURNER ORIFICE 6 TRANSFORMER 7 PILOT TUBING CONTROLS REFER TO UNIT WIRING DIAGRAM 8A MAIN GAS VALVE HONEYWELL 8B MAIN GAS VALVE WHITE RODGERS 9 HONEYWELL IGNITOR 10 HONEYWELL...

Page 18: ...old pressure of 3 5 inches W C 0 9 kPa Adjustment of the pressure regulator is not normally necessary since it is preset at the factory However field adjustment may be made as follows a Attach manomet...

Page 19: ...3 A proper pilot flame is a soft steady flame that envelopes 3 8 to 1 2 inch 9 5 to 12 7mm of the flame sensor tip 4 Replace the pilot adjustment cap PERIODIC SERVICE NOTICE It is recommended that the...

Page 20: ...e and replace Refer to Operation 1 Close air shutter Refer to Operation 2 Check with local gas supplier for proper orifice size and replace Refer to Operation 1 Close air shutter 2 Reduce pilot gas Re...

Page 21: ...and correct 5 Replace gas valve 6 Refer to Operation 1 Tighten all electrical connections 2 Adjust thermostat heat anticipator for longer cycles Refer to Operation 3 Check for proper air supply acros...

Page 22: ...late rating check voltage replace fan motor if defective 4 Refer to label on motor 1 Check all wiring 2 Refer to H or N symptoms 3 Replace fan switch 1 Refer to Operation 2 This is especially true whe...

Page 23: ...Check motor amps against motor name plate rating check voltage replace power venter motor if defective 4 Refer to label on motor 1 Check all wiring 2 Refer to H N symptoms 3 Replace venter relay X Pil...

Page 24: ...e 20 Internal Furnace Components Figure 21 Burner Assembly Parts Figure 19 Component Parts Bottom View MOTOR GAS VALVE IGNITOR ELECTRIC LIGHTING INSTRUCTIONS DATA PLATE PILOT ACCESS DOOR OBSERVATION P...

Page 25: ...400 units 6 dia flue outlet Increaser required To be supplied by manufacturer 25 REF NO DESCRIPTION 1 Blower Housing Assembly 2 Speed Nut 3 Motor 4 Washer Plain 5 Plate Adapter 6 Blower Wheel 7 Mounti...

Page 26: ...from the Power Venter Blower Housing Item 8 6 Remove the Blower Wheel Item 9 from the motor shaft by removing the set screw Item 14 using a 1 8 Allen Wrench 7 Remove the three Motor Mounting Nuts Item...

Page 27: ...uctions or has been altered or modified in any way by any unauthorized person b to any expenses including labor or material incurred during removal or reinstallation of the Product c to any damage due...

Page 28: ...contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GENERAL With power and gas off Make certain all packing has been removed Tigh...

Page 29: ...1 HP w Contactor S 1 HP w Magnetic Starter G 1 1 2 HP w Contactor T 1 1 2 HP w Magnetic Starter H 2 HP w Contactor U 2 HP w Magnetic Starter J 1 4 HP W 1 4 HP w Magnetic Starter K 1 3 HP Y 1 3 HP w M...

Page 30: ...NOTES 30...

Page 31: ...NOTES 31...

Page 32: ...260 NORTH ELM ST WESTFIELD MA 01085 TEL 413 568 9571 FAX 413 562 8437 www mestek com...

Reviews: