background image

19

MAINTENANCE

  3. To clean or replace the main burners, remove the 

bottom panel and compress the spring by moving         
the burner toward the manifold. Slide the opposite 
end of the burner downward from the locating slot       
while retaining spring is still compressed. Pull the      
burners away from the heater.

  4. With the burners removed, gently wire brush the 

inside surfaces of the heat exchanger.

  5.  Remove any dirt, dust, or other foreign matter from 

the burners using a wire brush and/or compressed 
air. Ensure that all parts are unobstructed. Inspect 
and clean pilot burner if necessary.

  6.  Reassemble the gas unit heater by replacing all    

parts in reverse order.

  7.  Complete the appropriate unit start-up procedure 

as given in the “Operation” section of this manual 
(see lighting instruction plate on the unit).

  8.  Check the burner adjustment. See the “Primary Air 

Shutter Adjustment” section of this manual.

  9.  Check all gas control valves and pipe connections        

for leaks.

10.  Check the operation of the automatic gas valve and 

the power venter assembly by lowering the setting 
of the thermostat, stopping the operation of the 
gas unit heater. The gas valve should close tightly, 
completely extinguishing the flame on the main 
burners.

11.  Inspect and service the motor/fan assembly. To 

maintain efficient air flow, inspect and clean the 
fan blades and guard to prevent buildup of foreign 
matter.

12.  Check lubrication instructions on the motor. If oiling 

is required, add 3 to 4 drops of electric motor oil as 
follows:

 

a.  Light Duty - After 3 years or 25,000 hours of 

operation.

 

b.  Average Duty - Annually after 3 years or 8,000 

hours of operation.

 

c.  Heavy Duty - Annually after 1 year or at least 

every 1500 hours of operation.

 Never over oil the motor or premature 

failure may occur!

13.  Check and test the operational functions of all 

safety devices supplied with your unit.

PILOT ADJUSTMENT
1.   Remove the pilot adjustment cap.
2.   Adjust the pilot screw to provide a properly sized 

fl ame.

3.   A proper pilot flame is a soft steady flame that 

envelopes 3/8 to 1/2 inch (9.5 to 12.7mm) of the 
fl ame sensor tip.

4.  Replace the pilot adjustment cap. 

PERIODIC SERVICE

NOTICE: It is recommended that the heater and 
vent system be checked once a year by a qualifi ed 
serviceman.

All Maintenance/Ser vice info should be recorded 
accordingly on the Inspection Sheet provided in this 
manual.

 Open all disconnect switches 

and disconnect all electrical and gas supplies 
and secure in that position before servicing 
unit. Failure to do so may result in personal 
injury or death from electrical shock.

 Gas tightness of the safety shut-

off valves must be checked on at least an annual 
basis.

To check gas tightness of the safety shut-off valves, turn off 
the manual valve upstream of the appliance combination 
control. Remove the 1/8 inch pipe plug on the inlet side 
of the combination control and connect a manometer to 
that tapping. Turn the manual valve on to apply pressure 
to the combination control. Note the pressure reading on 
the manometer, then turn the valve off. A loss of pressure 
indicates a leak. If a leak is detected, use a soap solution 
to check all threaded connections. If no leak is found, 
combination control is faulty and must be replaced before 
putting appliance back in service.

Should maintenance be required, perform the following 
inspection and service routine:
  1.  Inspect the area near the unit to be sure that 

there is no combustible material located within the                   
minimum clearance requirements listed in this                    
manual.

 Under no circumstances should 

combustible material be located within the 
clearances specified in this manual. Failure 
to provide proper clearance could result in 
personal injury or equipment damage from fi re.

  2.  Turn OFF the manual gas valve and electrical 

power to the gas unit heater.

MANIFOLD PRESSURE ADJUSTMENT
If the manifold pressure requires minor adjustment, 
remove the cap from the pressure regulator and turn 
the adjustment screw clockwise to increase the 
pressure, or counterclockwise to decrease the 
pressure. The adjusted manifold pressure should not 
vary more than 10% from the pressures specified in 
Table 4.

Summary of Contents for IIEB-11

Page 1: ...l operate and maintain unit in accordance with manufacturer s instructions to avoid exposure to fuel substances or substances from incomplete combustion which can cause death or serious illness The st...

Page 2: ...bled high static pressure type centrifugal blower unit designed for heavy duty applications such as continuous operation or where a single unit heater must do the entire heating job in a large area Th...

Page 3: ...ly with the general safety information may result in extensive property damage severe personal injury or death This product must be installed by a licensed plumber or gas fitter when installed within...

Page 4: ...94 1295 1295 1226 1295 1295 E Hanging Distance Width 14 1 2 17 1 4 17 1 4 20 22 3 4 25 1 2 28 1 4 33 3 4 39 1 4 44 3 4 368 438 438 508 578 648 718 857 997 1137 F Discharge Opening Width 15 3 8 18 1 8...

Page 5: ...as ignition system the unit heater must be installed such that the gas ignition control system is not directly exposed to water spray rain or dripping water NOTE Location of unit heaters is related di...

Page 6: ...r and can actually drip water down from the unit heater onto floor surface Additional unit heaters should be installed if a minimum 50 F 10 C thermostat setting cannot be maintained AIR FOR COMBUSTION...

Page 7: ...1 3 54 3 34 3 11 2 92 2 63 2 38 2 18 2 04 1 1 049 680 465 375 320 285 260 240 220 205 195 175 160 145 135 19 3 13 2 10 6 9 06 8 07 7 36 6 80 6 23 5 80 5 52 4 96 4 53 4 11 3 82 1 1 4 1 380 1400 950 770...

Page 8: ...al gas applications install a pressure regulating valve in the line upstream from the main shutoff valve 3 Adequately support the piping to prevent strain on the gas manifold and controls 4 To prevent...

Page 9: ...ER ASSEMBLY FOR THE 100 250 UNITS CONSISTS OF 1 WHEEL 1 HOUSING 1 SHAFT AND 1 BEARING SET FOR 300 400 UNITS THE BLOWER ASSEMBLY CONSISTS OF 2 WHEELS 2 HOUSINGS 1 SHAFT AND 1 BEARING SET Figure 7 Motor...

Page 10: ...ase motors require a contactor or starter if specified 4 Motor frame must not exceed NEMA frame 56 Average value all speeds and frequencies 10 327 345 362 380 397 414 431 448 466 483 500 518 535 552 5...

Page 11: ...re to disconnect power before servicing can cause severe personal injury or death Standard units are shipped for use on 115 volt 60 hertz single phase electric power The motor name plate and electrica...

Page 12: ...16 for special installation requirements regarding these venting conditions CARBON MONOXIDE Your venting system must not be blocked by any snow snow drifts or any foreign matter Inspect your venting...

Page 13: ...feet 1 2m from electric meters gas meters regulators and relief equipment Seal ALL vent pipe joints and seams to prevent leakage Use General Electric RTV 108 or Dow Corning RTV 732 silicone sealant or...

Page 14: ...14 Figure 13 Figure 14...

Page 15: ...15 Figure 15 Figure 16...

Page 16: ...fan switch delays the operation of the fan until the heater is warmed then keeps the fan running after the gas has been turned off until the useful heat has been removed The start up fan delay must no...

Page 17: ...4 BURNER SPRINGS 5 MAIN BURNER ORIFICE 6 TRANSFORMER 7 PILOT TUBING CONTROLS REFER TO UNIT WIRING DIAGRAM 8A MAIN GAS VALVE HONEYWELL 8B MAIN GAS VALVE WHITE RODGERS 9 HONEYWELL IGNITOR 10 HONEYWELL...

Page 18: ...old pressure of 3 5 inches W C 0 9 kPa Adjustment of the pressure regulator is not normally necessary since it is preset at the factory However field adjustment may be made as follows a Attach manomet...

Page 19: ...3 A proper pilot flame is a soft steady flame that envelopes 3 8 to 1 2 inch 9 5 to 12 7mm of the flame sensor tip 4 Replace the pilot adjustment cap PERIODIC SERVICE NOTICE It is recommended that the...

Page 20: ...e and replace Refer to Operation 1 Close air shutter Refer to Operation 2 Check with local gas supplier for proper orifice size and replace Refer to Operation 1 Close air shutter 2 Reduce pilot gas Re...

Page 21: ...and correct 5 Replace gas valve 6 Refer to Operation 1 Tighten all electrical connections 2 Adjust thermostat heat anticipator for longer cycles Refer to Operation 3 Check for proper air supply acros...

Page 22: ...late rating check voltage replace fan motor if defective 4 Refer to label on motor 1 Check all wiring 2 Refer to H or N symptoms 3 Replace fan switch 1 Refer to Operation 2 This is especially true whe...

Page 23: ...Check motor amps against motor name plate rating check voltage replace power venter motor if defective 4 Refer to label on motor 1 Check all wiring 2 Refer to H N symptoms 3 Replace venter relay X Pil...

Page 24: ...e 20 Internal Furnace Components Figure 21 Burner Assembly Parts Figure 19 Component Parts Bottom View MOTOR GAS VALVE IGNITOR ELECTRIC LIGHTING INSTRUCTIONS DATA PLATE PILOT ACCESS DOOR OBSERVATION P...

Page 25: ...400 units 6 dia flue outlet Increaser required To be supplied by manufacturer 25 REF NO DESCRIPTION 1 Blower Housing Assembly 2 Speed Nut 3 Motor 4 Washer Plain 5 Plate Adapter 6 Blower Wheel 7 Mounti...

Page 26: ...from the Power Venter Blower Housing Item 8 6 Remove the Blower Wheel Item 9 from the motor shaft by removing the set screw Item 14 using a 1 8 Allen Wrench 7 Remove the three Motor Mounting Nuts Item...

Page 27: ...uctions or has been altered or modified in any way by any unauthorized person b to any expenses including labor or material incurred during removal or reinstallation of the Product c to any damage due...

Page 28: ...contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GENERAL With power and gas off Make certain all packing has been removed Tigh...

Page 29: ...1 HP w Contactor S 1 HP w Magnetic Starter G 1 1 2 HP w Contactor T 1 1 2 HP w Magnetic Starter H 2 HP w Contactor U 2 HP w Magnetic Starter J 1 4 HP W 1 4 HP w Magnetic Starter K 1 3 HP Y 1 3 HP w M...

Page 30: ...NOTES 30...

Page 31: ...NOTES 31...

Page 32: ...260 NORTH ELM ST WESTFIELD MA 01085 TEL 413 568 9571 FAX 413 562 8437 www mestek com...

Reviews: