32
Chapter 6 • Inspection, maintenance, service
User Manual FSK700-2 / FSK700-2SX
6
Inspection, maintenance, service
This chapter contains advice for a trained service technician regarding inspection and maintenance
tasks to be performed on a Series FSK700 Key Safe, as well as information about possible mal-
functions, their causes and means of correction.
VdS-Richtlinie 2350, 6.1 Allgemeines: Key depots, key depot controlling and monitoring device,
unblocking device, and device parts of the controlling and monitoring device are to be inspected
each yearly quarter, and maintained at least once a year. At the minimum, all tasks according to
Anhang C "Instandhaltungsplan" of Richtlinie 2350 must be performed.
All maintenance tasks are to be entered in the report book of the alarm system.
To perform some of the following inspection, maintenance and service tasks, the outer door of
the Fire Brigade Key Safe must be opened with the key in possession of the local fire brigade or
public safety services. For this, the presence of local authorities or the fire brigade is generally
required! These requirements may, however, differ regionally.
6.1
Inspection, maintenance
During inspection or maintenance, the conditions listed in the table below are to be checked.
Check
Steps to take, if necessary
In
sp
ec
ti
on
a
n
d
m
ai
n
te
n
an
ce
1
Key Safe undamaged on the outside
Clean the outer surface
1)
2
Drill holes for water outlet on the bottom side must
be free of residue
Clean
3
Outer door: alignment, clearance, flexibility
Readjust, grease the bearings
4
Function of the closure device
- detent of the locking bolt
- tamper switch
- smooth action of the locking angle
- function of the magnetic door opening device
- proper self-aligning of the closure device
Clean and, if necessary, grease
sliding surfaces, replace faulty
parts
5
Door Protection Board undamaged (no scratches, cor-
rosion, connection cable undamaged)
If functioning is impaired:
replace
6
Function testing, including displays on the con-
trolling and monitoring device (excluding opening
the inner door and removing keys)
Fault correction
M
ai
n
te
n
an
ce
7
Fixedness of the Key Safe inside the Flush Mounting
Frame
Tighten nuts, correct construc-
tional problems
8
Connection cables undamaged, connectors connected
correctly, terminals fixed tightly
Replace damaged parts (such as
crushed cables, corroded com-
ponentry)
9
Inner door: clearance, bolt end stop, flexibility
Readjust, grease the bearings
10 Locking Cylinder Mounting Bracket(s):
- function of the micro switch
- smooth action
Clean and grease, replace faulty
parts
11 Smooth action of locks and locking cylinders
Apply precautionary measures
12 Measure the heater current (see page 29 and onwards
in chapter 5.4, section 4 Checking the outer door
heating device)
Eliminate the cause (e.g., heat-
ing power supply), replace faulty
parts
HB_FSK700_1020_9161690_Englisch_D.odt / 1022 D / AN9161690