background image

Part #85-03-00855

 

 

INSTALLATION INSTRUCTIONS 

 

CAUTION:

  Each installation must conform to all local, state and national codes. Refer to the national fuel gas code and local zoning and code authorities for details on 

installation requirements. The Mendota Inserts must be vented to the outside in accordance with the latest edition of the National Fuel Gas Code.  In the absence of local 
codes, the installation must conform with National Fuel Gas Code ANSI Z223.1 (NFPA 54), or Canadian Code CAN1-B149 or most current edition, also known as 
NFPA 54.  Do not connect this Insert to a chimney flue serving a separate solid fuel or gas-burning appliance. 

1.  Remove glass doors, metal fire screens, etc. from existing fireplace.  Be sure there is 12" minimum dis-

tance from top of upper grill to bottom of mantel; see Specifications (Pg.6 & 5), and a 16" minimum non-

combustible hearth extension in front of the glass surface if a raised hearth is not supplied.  (See pg. 11 

for "Raised Hearth"). 

 

2.  Remove any additional framework or other obstructions in the existing fireplace opening and burning area.  

Also remove any chimney cap from top of chimney so that vent liner can be installed freely. 

 

3.  Before Insert is installed, have gas supplier or contractor run gas line to the existing fireplace.  Be sure gas 

plumbing instructions [see Pg. 12 & 13

 

are carefully followed.  Gas supply may enter fireplace on either 

side or back of fireplace, whichever is most convenient and accessible.  Electrical service (120 volt) should 

also be supplied. 

 

4.  The entire chimney should be swept to remove creosote, soot and any obstructions (bird nests, etc.). 

 

5.  Open fireplace damper.  If damper opening is large enough to accept the 4" and 3" flue liners, permanent-

ly secure damper in "open" position.  NOTE:  

Massachusetts requires that the flue damper must be re-

moved or permanently welded in the "open" position. 

 

6.  If damper opening is too small for the 4" & 3" flue liners, it will be necessary to remove the damper handle 

and the damper plate.  Some damper plates are held in place by a pinned hinge that can be released easily 

by tapping out the pin with a hammer and punch.  Others may be held in place by a screw or bolt, or pi-

vots may be cast into the damper housing.  The latter types may be harder to get out and may require 

sawing or breaking out.  [NOTE:  if flue size is 6" (127 mm) or less, or if severe offsets occur, or a signifi-

cant mortar slop is evident between the liners, try to snake liner down the chimney to the top of the dam-

per housing before breaking out damper plate and housing.] 

 

 

CAUTION:  If the 4" & 3" flue liners cannot be installed in an extremely tight chimney DO NOT proceed 

with installation. 

7.  If damper opening is narrower than 4-1/2" to 5" (114 mm to 127 mm) and if local code authorities allow, 

loosen and remove mortar behind back side of damper housing in the center of the opening enough to get 

the gripping teeth of a pipe wrench over the flange of the damper housing (for cast iron housings).  Tigh-

ten the wrench snugly, and kick down on the wrench handle to break out a half moon shaped piece of the 

damper housing, enough to easily fit the flex liner through it.  If the opening is wide enough, the break out 

is not necessary. 

8.

 

Install Insert only in chimney heights of 12' (minimum) to 35' (maximum) -- as measured in 

step 9, below.  

9.

 

Measure the chimney height from the top of the chimney (or the existing flue liner) to a point 24" (610 

mm) above the floor of the fireplace hearth.  It may be necessary to drop a rope and measure the rope it-

self.  Be sure to allow for all offsets in existing chimney.  Cut the 4" diameter flex liner (s) to this measured 

length. 

Summary of Contents for E-FV44I ECHO SERIES

Page 1: ...l the fire department Installation and service must be performed by a qualified installer service agency or the gas suppli er WARNING Do NOT use this appliance if any part has been under water Immedia...

Page 2: ...OF OR OC 30 KEY LOCK FUNCTION 30 LOW BATTERY POWER DETECTION 30 OPERATING DURING POWER OUTAGES 30 FIRST TIME PILOT LIGHTING INSTRUCTIONS 31 INITIALIZING THE REMOTE CONTROL SYSTEM 31 SYNCHRONIZING RECE...

Page 3: ...W C MIN 11 W C MAX L P GAS 11 W C 11 W C MIN 13 W C MAX ELECTRICAL REQUIREMENTS 120 Volts AC 2 Amps minimum line voltage allowed 110 Volts AC LISTINGS INTERTEK TESTING SERVICES TESTED TO ANSI Z21 88 2...

Page 4: ...he hazards of high surface temperature and should STAY AWAY to avoid burns or clothing ignition Young children should be CAREFULLY SUPERVISED when they are in the same room as the appliance These unit...

Page 5: ...t annually by a professional service person More frequent cleaning may be required due to excessive lint from carpeting bedding material carbon build up etc It is imperative that control com partments...

Page 6: ...if situated to maximize heat circulation NOTE The Mendota Insert is designed as a supplemental heat source It should not be used as a whole house heating system Supplemental air movement consideratio...

Page 7: ...from the solid fuel fireplace to accommodate the gas insert Smoke shelves shields and baffles can be removed if attached with mechanical fasten ers Trim panels and surrounds shall not seal ventilation...

Page 8: ...nent ly secure damper in open position NOTE Massachusetts requires that the flue damper must be re moved or permanently welded in the open position 6 If damper opening is too small for the 4 3 flue li...

Page 9: ...the existing chimney damper about 2 feet Pack around the liners at the damper area to create an air tight seal In the USA do not run the 3 air intake liner to the Vertical Cap NOTE THE INSERT IS DESIG...

Page 10: ...it Two installers should proceed to the roof and drop the rope with weight on the end to make sure it goes all the way down and insert the 4 liner s past the flexible portion into the existing chimney...

Page 11: ...ut and connect to a grounded wall outlet 17 Slide Vent Adapter forward between guide rails Vent Adapter s front flat section should contact insert top as you slide the Vent Adap ter forward 18 Use Gla...

Page 12: ...g fireplace opening IMPORTANT INSTALLATION SERVICING AND REPAIR MUST BE DONE BY A QUALIFIED SERVICE PERSON THE INSERT SHOULD BE INSPECTED AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON MORE FREQUE...

Page 13: ...SOAP WATER SOLUTION BE SURE TO INSTALL FLEX GAS LINE WITH BRASS TO BRASS FITTINGS TO PREVENT GAS LEAKS AT CONNECTIONS GAS SUPPLY PIPING MUST INCLUDE A DRIP LEG TO ELIMINATE THE POSSIBILITY OF CONTAMI...

Page 14: ...KPA the appliance must be isolated from its supply with an approved ma nual shut off cock This manual shut off cock must be closed during any supply line pressure testing Check with your gas supplier...

Page 15: ...SSURE NATURAL GAS 7 0 W C 1 75 kPa 5 0 W C 1 12 kPa 11 W C 2 61 kPa L P GAS 11 0 W C 2 75 kPa 11 W C 2 75 kPa 13 0 W C 3 24 kPa TURN GAS VALVE KNOB TO HIGH POSITION GAS PRESSURES MAY VARY PLUS OR MINU...

Page 16: ...arying altitudes the information sticker must be filled out by the installer and ad hered to the appliance at the time of conversion Cet appareil est equip pour des altitudes compries entre 0 et 2000...

Page 17: ...in this appliance including field installed supply line fittings and all factory installed gas train connections between the gas valve and the burner orifice s and pilot light must be leak tested pri...

Page 18: ...the panel s should be done by a licensed or qualified service person To Unlatch Glass Frame Latches 1 Insert Glass Latch Tool into hole in latch two latches exist at top of glass frame 2 Pull Glass La...

Page 19: ...55 18 FV 44i LOG SET INSTALLATION INSTRUCTIONS FOLLOW EACH STEP DEPICTED IN THE DIAGRAMS BELOW TO INSTALL THE LOG SET CAUTION LOGS ARE FRAGILE HANDLE LOG PIECES WITH CARE FV 44i LOG SET PARTS IDENTIFI...

Page 20: ...Part 85 03 00855 19...

Page 21: ...Part 85 03 00855 20...

Page 22: ...Part 85 03 00855 21...

Page 23: ...Part 85 03 00855 22...

Page 24: ...Part 85 03 00855 23...

Page 25: ...Part 85 03 00855 24...

Page 26: ...Part 85 03 00855 25...

Page 27: ...Part 85 03 00855 26...

Page 28: ...Part 85 03 00855 27 PLACE SMALL COALS ON TOP OF FLOOR BRICK PANELS AND CLOSE TO GRATE BOTTOM TO SIMULATE A COAL BED...

Page 29: ...s mode Other functions such flame height control will be manually controllable b Normal Thermostat In this mode the fireplace will stay functioning until the room temperature increases 1 o F above the...

Page 30: ...rge Set Temperature is dis played Pressing the Up or Down button once in this mode will increase or decrease the set temperature Note that the large temperature display in the center of the screen is...

Page 31: ...ER DETECTION 1 Transmitter Batteries The life span of the remote control transmitter batteries depends on various factors quality of the batteries used the number of ignitions of the appliance the num...

Page 32: ...il the pilot flame lights and the pilot is burning steadily After you inspect the spark and the pilot lights turn off the pilot switch and close the glass door 8 Relight Pilot after closing glass door...

Page 33: ...teries into the Remote Receiver s battery compartment toggle the Pilot Light ON OFF switch to the OFF position Toggle the switch DOWN to OFF If the Pilot Light ON OFF switch is left in the ON position...

Page 34: ...Part 85 03 00855 33 FV 44i GAS IGNITION SYSTEM WIRING DIAGRAM...

Page 35: ...ns on PAGE 34 C Check condition of glass door gasket gasket must seal tightly over firebox replace if necessary D Periodically check to verify that the vent system and vent cap are open and free of bl...

Page 36: ...prior to disconnecting the electrical power ORIFICE SIZES REQUIREMENT A Natural Gas to LPG conversion kit HA 58 00302 must be ordered and installed to convert the FV 44i Fireplace to burn LPG LP Conve...

Page 37: ...lve body in the same position and orientation as the NG Pressure Regulator you removed in Step 2 above The LP Pressure Regulator can only be mounted in one position Secure the LP Pressure Regulator in...

Page 38: ...RE REGULATOR CONVERSION INSTRUCTIONS WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifical ly approved with this appliance may result in prope...

Page 39: ...soap and water solution at all plumbing joints prior to placing this appliance into operation It is recom mended that all gas plumbing joints factory installed and field installed are checked for leak...

Page 40: ...n for proper rating methods If the installer must convert the unit to adjust for varying altitudes the information sticker must be filled out by the installer and adhered to the appliance at the time...

Page 41: ...n Emergency Gas Shutoff Control that is designed to be activated using the glass latch tool The shutoff valve and the control is located on the left side of the appliance behind the remote control rec...

Page 42: ...nd their dealers are not responsible for damage caused by excessive sooting that has not been immediately brought to their attention AGA ANSI APPROVAL Gas appliances must be tested and certified by a...

Page 43: ...se in small 1 8 increments until flame turns desired realistic orange 3 If flame is too orange or is causing sooting on viewing glass pull air shutter knob out open in approx 1 8 incre ments until soo...

Page 44: ...TS LIST ITEM QTY PART NUMBER DESCRIPTION 1 1 65 14 00042 Front ORIFICE 42 NATURAL GAS 2 2 65 07 00024 1 8 NPT to Flex CF Coupler 3 1 05 04 00050 SIT Pilot Assembly 4 2 65 14 00045 Rear ORIFICE 45 NATU...

Page 45: ...ED Per Manual and manufacturer s specifications CHECK FOR PROPER CLEARANCES TO COMBUSTIBLES Per pipe manufacturer s specifications INSTALL PROPER SIZE GAS LINES CHECK FOR GAS LEAKS Per Manual CHECK FO...

Page 46: ...Part 85 03 00855 45 TAPE SHUT JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 POSTAGE NEEDED...

Page 47: ...his warranty does not cover glass or log breakage Mendota has the right to investigate and inspect the exact original fireplace and materials in the event a claim is made without alterations or tamper...

Page 48: ...Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 Website www johnsongas com or www mendotahearth com...

Reviews: