LP GAS PRESSURE REQUIREMENTS
Inlet and manifold gas pressure checking taps are located on gas valve. These ports are only accessible from the outer
left side of the fireplace. A qualified installer shall take pressure measurements at these ports to verify and set the correct
gas pressures during the LP Kit installation and before facia materials are installed over the front of this fireplace.
Manifold
pressure must be taken at the “MANIFOLD PRESSURE" tap and inlet pressure at the "INLET PRESSURE" tap
with the
burner
operating
by a qualified installer.
DESIRED
INLET
PRESSURE
MINIMUM
INLET
PRESSURE
MAXIMUM
INLET
PRESSURE
MANIFOLD
OUTLET
PRESSURE
AIR SHUTTER
POSITION
L.P. GAS
11.0" W.C
.
(2.75 kPa)
11" W.C.
(2.75 kPa)
13.0" W.C.
(3.24 kPa)
10.0" W.C.
(2.5 kPa)
1/4" OPEN MIN.
(5 mm)
REGULATE THE FLAME HEIGHT TO "HIGH" POSITION. OUTLET GAS PRESSURES MAY VARY PLUS OR MINUS 5%.
LPG PROPER INPUT RATES:
With the proper orifices installed, as specified above, this
fireplace utilizing LP Gas will have a maximum input rate of
40,000 Btu/Hr.
LEAK TESTING REQUIREMENTS
Prior to completing the conversion process
, c
heck for gas
leaks with soap and water solution at all plumbing joints
prior to placing this appliance into operation. It is recom-
mended that all gas-plumbing joints, factory installed and
field installed are checked for leaks.
PILOT FLAME AND MAIN BURNER
RELATIONSHIP VERIFICATION
Prior to completing the conversion process, the qualified
service technician must, light the pilot light and verify the relationship between the
pilot light flames and the main burners. The pilot light flames directed towards the propagation ports on the rear and front
burner must overlap the propagation ports on the burners. The pilot light flames must be a minimum of ¾” long and must
overlap the propagation ports on both the rear and front burners as shown in the diagram, below. Verify that the burner
tubes ignite quickly and the burner flames propagate smoothly along the entire length of the burners.
PILOT FLAME LENGTH ADJUSTMENT
If the pilot light flame length is too short and the system does not maintain a standing pilot, a qualified installer may in-
crease the length of the pilot light flames to meet the two requirements: Minimum pilot light length to maintain a standing
pilot light and the pilot light flames must be long enough to overlap the front and rear burner ports.
Figure 1: Pressure Test Port
1" MIN.
1" MIN.
1" MIN.
Pilot Flame
must overlap
Burner Ports
Summary of Contents for E-FV44I ECHO SERIES
Page 20: ...Part 85 03 00855 19...
Page 21: ...Part 85 03 00855 20...
Page 22: ...Part 85 03 00855 21...
Page 23: ...Part 85 03 00855 22...
Page 24: ...Part 85 03 00855 23...
Page 25: ...Part 85 03 00855 24...
Page 26: ...Part 85 03 00855 25...
Page 27: ...Part 85 03 00855 26...
Page 34: ...Part 85 03 00855 33 FV 44i GAS IGNITION SYSTEM WIRING DIAGRAM...