InfiniBand FDR Switch Platform Hardware User Manual
Mellanox Technologies
54
2. Slowly slide in the new leaf fan module.
3. Push the fan module until the latch engages.
4. Make sure that the green leaf LED on the module comes on (indicating that fan is
running).
1.10.4.2 Spine Fan Modules
Each spine module has a fan module with two individual fans built in. When a fan mod-
ule is not functioning the Fan Status LED on the spine will light up.
Figure 49: Spine Fan Module
When a fan module is removed the indicator light will reset.
Figure 50: Fan Status LED on the Spine Module
Extracting the Spine Fan Module
1. Push the two blue latch buttons together while pulling the fan module out.
Inserting the Spine Fan Module
1. Make sure the fan module is oriented correctly top side up. Confirm that the location
of the connector in the chassis will line up with the connector in the fan module.
If the fan module stops before it goes in all of the way it is inserted incorrectly or it
may be for the other side of the chassis!
When hot-swapping any of the units, it is necessary to wait 1 minute after removing
the defective part before inserting the new part. This is necessary so that the manage-
ment module will start a new cycle checking through the leafs and spines for the FW
versions.
1 3 5 7 9 11 13 15 17
2 4 6 8 10 12 14 16 18
19 21 23 25 27 29 31 33 35
20 22 24 26 28 30 32 34 36
!
!
UID
Fan module
1 3 5 7 9 11 13 15 17
2 4 6 8 10 12 14 16 18
!
!
UID
Fan status LED