InfiniBand FDR Switch Platform Hardware User Manual
Mellanox Technologies
24
Figure 5: Vertical Rack Supports Dimension
3. Decide which side of the rack you want the data connectors.
Figure 6: Placement of Chassis in Rack
You will most likely need extra room for cable bending on the connector side of the chassis
and should plan to keep the spine side as close to the rack door as possible, thus having more
room for the cables.
4. Measure the distance between the vertical supports and adjust the shelf brackets
according to this distance. This chassis can be installed in a rack with a distance
between the vertical supports of from 65cm(25.6in.) to 80cm(31.5in.).
65-
80
cm
Vertical
supports
19" (482.6mm)
Chassis
Shelf
Connector side
Spine side
Cable with
recommended
bending radius
Insufficient room for recommended
bending radius
Doors
Doors