Mellanox Grid Director 4700 Installation Manual
29
This formula provides margin for momentary power peaks and enhances reliability by
preventing the power subsystem from continuously operating at maximum power.
3.
For redundancy (N:1 or N:N), configure additional power supplies.
Table 10: Module Power Data
Mellanox Grid Director™ 4700
Description
Module Name
DC Power Consumption
[Watt] (*)
Basic chassis configuration
Single management board
Horizontal fan units
Vertical fan unit
Two power supply units
4700
sMB
sFU-40H
sFU-40V
2 x sPSU-S
675.0
sFB, 9-QDR-connections fabric board
sFB
990.0
sMB
sMB-CM
45.0
Modules for the Mellanox Grid Director™ 4700
Description
Module Name
DC Power Consumption [Watt]
sLB-4018, 18 QSFP ports per sLB-4018
sLB-4018
110.0
(*) Add 1.5 Watts for each connected QSFP optical module
Spare Parts for the Mellanox Grid Director™ 4700
Description
Module Name
DC Power Consumption
[Watt]
sFU-40H, Horizontal Fan Unit
sFU-40H
380.0
sFU-40V, Vertical Fan Unit
sFU-40V
250.0
3.10
Calculating Heat Output in BTUs
To compute the approximate BTUs for a given configuration, find the power consumption in
Watts (e.g., from Power Data Per Module;
see
), and multiply by 3.408. Example calculations
for specific configurations are shown in the following table.
Table 11: BTUs for QDR Sample Configurations
Configuration
Modules Included
Power (Watts)
Heat Output
(BTUs)
18 ports per sLB-4018
9 sFB-4700, 1 sLB-4018, 1 sFU-40H, 1
sFU-40V, 1 sMB, 2 sPSU-S
2,041W
6,965
108 ports (6 sLBs x 18
port per sLB)
9 sFB-4700, 6 sLB-4018, 1 sFU-40H, 1
sFU-40V, 1 sMB, 2 sPSU-S
2,674W
9,123