Technician Settings (Cont’)
P192 – Temperature set-point for re-heat in unoccupied mode
Range: 10...30ºC / 50...86ºF
Default: 15ºC / 59ºF
P194 – Humidity differential band
Range: 0...10 %RH
Default: 5%RH
P193 – Display switching time (between temperature and humidity)
Range: 0...11 seconds
Default: 5 seconds
Set-point for reheat
in unocc. mode
Display switching
time Hum./Temp.
Humidity differential
band
P189 – Dehumidification cycle in unoccupied mode
Range: 0...600 minutes
Default: 20 minutes
P190 – Dehumidification break time in unoccupied mode
Range: 0...900 minutes
Default: 40 minutes
Dehumidification
cycle in unocc. mode
Dehumidification
break in unocc. mode
- 58 -
(°F)
(°C)
P188 – Room temperature limit for disabling dehumidification in
unoccupied mode
Range: 10...30ºC / 50...85ºF
Default: 18ºC / 64ºF
Temp. for disabling
dehum. In unocc mode
(°F)
(°C)