HC22
1 Speed fan,
Humidifier,
Reheat for
Dehumidification
11
12
13
14
15
16
Heat element 2
(2
nd
stage heat)
Fan (1 speed)
Compressor 2
Compressor 1
(3)
-
HP31
1 Speed fan,
Humidifier,
Reheat for
Dehumidification
Fan (1 speed)
Compressor
(3)
Heat pump
(2)
8
7
6
5
4
3
2
1
6
5
4
3
2
1
SW3
SW1
8
7
6
5
4
3
2
1
Fan on/off: 110-230VAC, 2.5A max., Humidifier: 0-10VDC, 0.5mA Not isolated
Control - Heat elements, Heat pump, Compressors, Economizer: 110-230VAC, 0.3A max.
Wiring and DIP Switches – AC systems
w/wo Humidifier for humidification, with Reheat for dehumidification
Heat element 2
(3
rd
stage heat)
Heat element 1
(2)
(2
nd
stage heat)
-
6
5
4
3
2
1
HC11
2/3 Speeds fan,
Humidifier,
Reheat for
Dehumidification
Compressor
(3)
8
7
6
5
4
3
2
1
-
6
5
4
3
2
1
Fan medium
(or Economizer
(5)
)
Fan high
Fan low
Heat element 1
(2)
(1
st
stage heat)
Heat element
(2)
8
7
6
5
4
3
2
1
6
5
4
3
2
1
HP21
2/3 Speeds fan,
Reheat for
Dehumidification
Compressor
(3)
Heat pump
(2)
8
7
6
5
4
3
2
1
6
5
4
3
2
1
Fan medium
(or Economizer
(5)
)
Fan high
Fan low
Heat element
(2)
(2
nd
stage heat)
10
11
12
13
- 23 -
AO1
AO2
-
-
-
-
-
Humidifier
Humidifier
Humidifier
(1)
SW3.1, SW3.2 = Fan speeds: 2 Speeds (Low and High):
SW3.1 OFF, SW3.2 ON
3 Speeds (Low, Med. and High): SW3.1 OFF, SW3.2 OFF
(2)
SW3.4 = HP (Heat pump):
ON – Heat pump active in cool, OFF – Heat pump active in heat
HC (Not Heat pump): ON – Electrical heater,
OFF – Oil/Gas heater (no fan)
(3)
SW3.5 = Compressor delay:
ON – Disable compressor delay, OFF – Enable compressor delay
(5)
SW1.6 = Terminal 12 operation: ON – Economizer
OFF – Fan Med. (3 Speeds) / Terminal not in use (2 Speeds)
Important: Economizer will not work in 3 fan speeds configuration