Heat differential band
Technician Settings (Cont’)
ON
OFF
Room
Temp.
P47-48
Heat differential band / offset
(with heat differential band offset = 0)
Compressor / Valve
Set point
Heat differential band
P47-48
Heat differential band / offset
(with heat differential band offset
≠
0)
Compressor / Valve
ON
OFF
Room
Temp.
Set point
Heat differential band
Offset
(°F)
(°C)
Heat differential band offset
(°F)
(°C)
- 46 -
P47 – Heat differential band
Range: 0.5...5°C
/
1…10°F
Default: 1°C
/
2°F
P48 – Heat differential band offset
Range: -5…+5°C
/
-9…+9°F
Default: 0°C
/
0°F