Technician Settings (Cont’)
P83 – View T2 temperature sensor readings
Note:
If T2 is not connected, -9.9 will appear on display
T2 Sensor
readings
T2 Sensor
Not connected
P84 – View T3 temperature sensor readings
Note:
If T3 is not connected, -9.9 will appear on display
T3 Sensor
readings
°F
T3 Sensor
Not connected
P85 – Deice in cool – cut-in temperature (AC only!)
Range: -9.5…+8°C / 15...46°F
Default: 0°C / 32°F
P86 – Deice in cool – cut-out temperature (AC only!)
Range: 2...20°C / 36...68°F
Default: 8°C / 46°F
Deice in heat
time
Deice in heat
break time
Deice in cool
(°F)
(°C)
Deice in cool
(°F)
(°C)
The indoor unit coil temperature in which deicing will stop.
The indoor unit coil temperature in which deicing will start.
The length of deicing procedure.
The time interval between deicing cycles.
- 53 -
P87 – Deice in heat time (AC only!)
Range: 2...7 Minutes
Default: 5 Minutes
P88 – Deice in heat break time (AC only!)
Range: 10...30 Minutes
Default: 25 Minutes