Technician Settings (Cont’)
ON
OFF
Room
Temp.
P45 – P46
Cool differential band / offset
(with cool differential band offset = 0)
Compressor / Valve
Set point
Cool differential band
P45 – P46
Cool differential band / offset
(with cool differential band offset
≠
0)
Compressor / Valve
ON
OFF
Room
Temp.
Set point
Cool differential band
Offset
Cool differential band
(°F)
(°C)
Cool differential band offset
(°F)
(°C)
- 45 -
P45 – Cool differential band
Range: 0.5...5°C
/
1…10°F
Default: 1°C
/
2°F
P46 – Cool differential band offset
Range: -5…+5°C
/
-9…+9°F
Default: 0°C
/
0°F