6 System Installation
2.
High voltage peaks (e.g. caused by lightning strikes)
can be transmitted via the antenna cable and may
cause damage to the receiver. The receiver is pro-
tected against these effects by using the MBG S-PRO
surge protection.
Being installed in a waterproof housing, the MBG
S-PRO is also suitable for outdoor installation. Mein-
berg recommends the indoor installation, as soon as
possible after the antenna cable enters the building to
minimize the risk of overvoltage damage, e.g. due to
lightning strikes.
N-Norm (male)
N-Norm (female)
Outside wall of the building
Outdoor installation
Inside a waterproof housing.
Indoor installation
(recommended)
Just after the antenna cable enters
N-Norm (female)
N-Norm (male)
MBG S-PRO
MBG S-PRO
the wall.
3.
To ground the antenna cable, connect the surge
protection with a grounding cable to a equipotential
bonding rail (see figure).
After installation, connect the other end of the
antenna cable to the socket of the surge protection.
Earth cable to PE rail
Cable circa 1,5 mm Ø
attached to the surge protection
as short as possible
IMS - LANTIME M4000
Date: 27th May 2021
39