![Megmeet MTC-04-NT User Manual Download Page 12](http://html1.mh-extra.com/html/megmeet/mtc-04-nt/mtc-04-nt_user-manual_1765695012.webp)
12
BFM
Content
Remarks
Nature Save
CH1 CH2
CH3
CH4
#1149 #1150 #1151 #1152 Set change rate limit
rise * 10
Default value
:
0
Range:0~range,
Unit
:℃
/second
R/W
Y
#1157 #1158 #1159 #1160 Set change rate limit
drop * 10
Default value
:
0
Range:0~range,
Unit
:℃
/second
R/W
Y
#1165 #1166 #1167 #1168
Selection of
temperature control
object characteristics
* 11
Default value
:
0
0:Slow heating object
1:Slow heating object
R/W
Y
#1173 #1174 #1175 #1176 PID algorithm
selection
Default value
:
1
0:Fuzzy PID algorithm
1:Intelligent PID algorithm
R/W
Y
#1181 #1182 #1183 #1184 PID output upper limit
setting
Default value
:
0.0%
Setting
range:0.0%~100.0%
R/W
Y
#1189 #1190 #1191 #1192 PID output lower limit
setting
Default value
:
0.0%
Setting
range:0.0%~100.0%
R/W
Y
#1197 #1198 #1199 #1200 PID output dead zone
Default value
:
0.0%
Setting
range:0.0%~100.0%
R/W
Y
#1205 #1206 #1207 #1208
Manual / automatic
bumpless switching
setting * 12
Default value
:
0
0:Turn off bumpless
switching
1:Turn on bumpless
switching
R/W
Y
* 1. #901 ~ #904: input type selection. Select the input type and temperature mode of each channel, #901
corresponds to channel 1, #902 corresponds to channel 2, and so on. When the channel is set to 0, the
channel is closed and the corresponding channel does not perform A/D conversion. The meaning of the
pattern is shown in table 1-10.
Table1-10 Model specification
NO.
value
(decimal)
Significance
1
1
K-type thermocouple input range:
-
100.0
~
200.0
℃
2
2
K-type thermocouple input range
:-
100.0
~
400.0
℃
3
3
K-type thermocouple input range
:-
100.0
~
1200.0
℃
4
4
K-type thermocouple input range
:-
148.0
~
800.0
℉
5
5
K-type thermocouple input range
:-
148.0
~
2192.0
℉
6
6
J-type thermocouple input range
:-
100.0
~
200.0
℃
7
7
J-type thermocouple input range
:-
100.0
~
400.0
℃
8
8
J-type thermocouple input range
:-
100.0
~
600.0
℃
9
9
J-type thermocouple input range
:-
148.0
~
752.0
℉
10
10
J-type thermocouple input range
:-
148.0
~
1112.0
℉
11
11
E-type thermocouple input range
:-
100.0
~
200.0
℃
12
12
E-type thermocouple input range
:
0.0
~
850.0
℃
13
13
E-type thermocouple input range
:-
148.0
~
1562.0
℉
14
14
N-type thermocouple input range
:-
100.0
~
1200.0
℃
15
15
N-type thermocouple input range
:-
148.0
~
2192.0
℉
16
16
T-type thermocouple input range
:-
200.0
~
200.0
℃
17
17
T-type thermocouple input range
:-
200.0
~
300.0
℃
18
18
T-type thermocouple input range
:
0.0
~
300.0
℃
19
19
T-type thermocouple input range
:-
328.0
~
400.0
℉
20
20
T-type thermocouple input range
:-
328.0
~
572.0
℉