How to Perform a Test
AVTMST16 Rev 1 May 2016
27
Step Description
In case the software
cannot determine
the end of the cable, a message will be
displayed stating “CABLE END NOT CLEARLY VISIBLE” and offering to proceed by
“IGNORE” this fact.
Do
NOT
acknowledge
the IGNORE message, but turn to the
icon asking to
perform a manual adjustment of the End Marker by activating the END MARKER icon in
the feature menu. After adjustment to identify the cable end manually, click again and
acknowledge the manually identified cable end.
2
Select
to start the fault pre-location.
3
If required, the surge voltage can be adjusted through the
menu item. Otherwise,
the maximum surge voltage is automatically used, if default AUTOMATIC VOLTAGE
CONTROL.
4
Press the green illuminated “HV ON” button
.
5
Select
to charge the capacitor (only if
Measurement Start
option is set to
Manual.
See page 18).
Result:
The surge capacitor is charged up to 16 kV.