AVTMST16 Rev 1 May 2016
21
5
HOW TO PERFORM A TEST
Detecting and Locating a Cable Fault in a Shielded Medium
Voltage Power Cable
Locating a Faulty Cable Section (Sectionalizing)
Introduction
The sectionalizing technique is used to trouble shoot a distribution loop circuit in
order to identify the faulted section, so it can be quickly switched out, and the
rest of the circuit can be re-energized to provide service to all customers.
For this purpose, a LV reflection image is taken and scanned for impedance
changes which are related to the cable end and transformers. A second reflection
image of the TDR pulse is taken while an electrical arc is ignited by a sudden
discharge of the charged capacitor at the fault location. This reflection is
negative.
With both traces lying on top of each other, the fault location (position where
the two traces diverge from each other) is identified and the transformers
reflections provide the landmarks to identify the faulted cable segment. It will be
switched out by pulling the elbows to the left and right side of the fault. Service
to all customers is provided by closing the normally open point within the
distribution loop.
2 Alternatives
The procedure called “Sectionalizing” in the configuration set up will
work flow
perform the following steps:
Pattern 1
low voltage TDR trace to identify cable end (blue trace)
low voltage trace to identify all transformers in the faulted (half) loop (blue
trace)
high voltage trace to identify fault (negative reflection in red trace)
Summary of Contents for SMART THUMP ST16
Page 2: ...M ...
Page 3: ...Portable Fault Locating System SMART THUMP ST16 User Manual ...
Page 6: ...M M ...
Page 10: ...M AVTMST16 Rev 1 May 2016 iv M ...
Page 46: ...M AVTMST16 Rev 1 May 2016 36 M ...
Page 52: ...M AVTMST16 Rev 1 May 2016 42 M ...
Page 56: ...M AVTMST16 Rev 1 May 2016 46 ...
Page 58: ...M AVTMST16 Rev 1 May 2016 48 M ...