Connection Diagram
The following figure shows the simplified connection diagram.
Connection Sequence
Connect the unit in the following order:
Step Description
Connect the safety ground lead
to a reliable ground (e.g. station-ground,
transformer ground rod. Do not drive a separate ground rod!).
Connect the HV return lead
to the cable shield or the concentric neutral of the
specific cable to be tested. The resistance between the HV return (operational
ground) and the safety ground should be less than 5
Ω
(check with ohmmeter, if
questionable), if not the F-OHM safety feature will be activated, disabling the HV
ON function or activating the HV OFF function.
NOTE:
The closer and better the HV return is connected to the
shield / concentric of the cable to be tested, the better the
TDR trace readings will be.
Connect the HV lead
to the phase conductor to be tested (optional elbow
adapter or vice-grip.
(See 'Available Accessories' in Section 2).
Connect the supplied power cord
to the connector
on the back of the unit
and connect the other end to a power outlet.
NOTE:
If no power connection can be established, the unit can be
operated from the internal battery, provided it is equipped
with this feature and is properly charged. The unit also
provides 2 battery terminals that are accessible from the
out-side, which can be connected to an external battery
Only after all necessary connections have been made,
the ground connection
to the cable under test can be lifted.
110 V … 230 V
±15%,
50 / 60 Hz
Summary of Contents for SMART THUMP ST16
Page 2: ...M ...
Page 3: ...Portable Fault Locating System SMART THUMP ST16 User Manual ...
Page 6: ...M M ...
Page 10: ...M AVTMST16 Rev 1 May 2016 iv M ...
Page 46: ...M AVTMST16 Rev 1 May 2016 36 M ...
Page 52: ...M AVTMST16 Rev 1 May 2016 42 M ...
Page 56: ...M AVTMST16 Rev 1 May 2016 46 ...
Page 58: ...M AVTMST16 Rev 1 May 2016 48 M ...