23
7
General instructions for using the mobile unit
7.1
Configuring the Mobile Unit
Before a device can be put into operation as a mobile unit, the device settings under
Configuration
Settings
must first be opened and if necessary adjusted:
Parameter Description
Mode
Defines the mode the device operates in.
Because the basic hardware and software are the same, any device
in a PVS 100i system can be used as base station or mobile unit.
For the mobile unit, the
Mobile
option has to be selected.
Nr. Base
Phone number of the base station.
It is recommended to enter the call number including the international
calling code (e.g. +49XXXXXXXXXX). That way, the PVS 100i can
also be operated abroad.
SerNr. Base
Serial number of the HV sensor.
Before a PVS 100i unit can interact with a HV sensor, the serial
number of the HV sensor has to be entered here. Thus, it can be
ensured that the PVS 100i does not evaluate the signals transmitted
by other sensors. The serial number can be found on a label on the
HV sensor (e.g.
SN: 1480438771
).
HV sensor
type
The 7-digit item number of the HV sensor.
Before using the HV sensor, its item number must be entered here.
This provides the device with the sensor’s country-specific radio
frequency.
The serial number can be read from a sticker on the sensor (e.g.
PN:
1006488
).
Easy menu
By pressing the
Config
button, individual measurement profiles can
be assigned to the eight buttons of the quick selection menu (see
section 7.1).
In order to assign a measurement profile to one of the buttons, you
need to select the respective button first. Afterwards, the required
profile can be selected from the file browser. The file browser view
can be filtered as follows:
LV
LV measurement profile (file extension
.MSL
)
HV
HV measurement profile (file extension
.MSH
)
KAP
capacitive measuring point (file extension
.MSC
)