11
3.2
Technical Data
The PVS 100i is specified by the following technical parameters:
Parameter
Value
Operating voltage
115 V / 230 V AC 50/60 Hz
Power consumption
100 VA
Battery
Lithium ion (12.6 V; 4.8 Ah)
Battery life
10 hours
Input voltage range of
measurement input U
X
5 V … 400 V
Operating temperature
-20 °C ... +50 °C
Storage temperature
-40 °C ... +60 °C
Dimensions
(W x H x D)
235 mm x 105 mm x 181 mm
Weight
3.2 kg
Precision
•
up to 400 V
•
up to 120 kV
±0,5°
±10°
Display
LCD touch screen
240 x 128 pixels (transflective display)
Memory
1 GB SD card
Interfaces
USB (Host)
GSM (900/1800 Mhz)
Radio (868/915 MHz)
Protection rating
IP 54 (with the housing closed)
IP 20 (open)
Measurement Category
according to IEC-61010
CAT IV 300 V (using the fused crocodile clips)
CAT II 300 V (without the fused crocodile clips)
High voltage sensor
(HVS 120/36i)
•
Built-in wireless modem
868/915 MHz (depending on country)
•
Maximum voltage
120 kV system voltage (70 kV phase to earth)
•
Protection against flash
over initiation and bridging
according to EN 61243-1
36 kV
•
Power supply
Integrated NiMH accumulator
(operating time approx. 7 h)
•
Dimensions (Ø * L)
85 x 220 mm
•
Weight
0.9 kg
•
Protection rating
IP 43