72
15
Enter a voltage 1V and 300V that is less than the knee point of the CT
16
Hit Blue Play button to begin test.
17
The Ratio Test will begin.
X Voltage (V): The MRCT displays the real time voltage readings of the secondary X winding
while the test is in progress.
X Current (A): The MRCT the real time current readings for the secondary X winding while the
test is in progress.
H Voltage (V): The MRCT the real time voltage readings of the primary H winding while the test
is in progress.
19.
At any point of time Test can be terminated by hitting the ABORT button at the top
of the screen.
Figure 47: CT Ratio Test Abort
20.
Test can also be stopped under emergency condition by hitting the “Emergency Push
to Stop” button on the front panel of MRCT. Unit will shut off the output voltage
21.
After releasing the Emergency Stop Button, the test will need to be restarted.
22.
Upon completion of test, the results can be viewed in the test screen or in a test
report.