Measurement Technology NW
LCI-90 Operator Manual
Page 26
Figure 5.2 – LCI 90 Menu Tree
5.3
Alarms
The LCI-90 provides the user with up to six optional visual alarms that can be configured to
indicate high and low conditions of Tension, Payout, and line Speed. Each alarm can be
assigned to any of the three measured variables, and can be designated as a high or low
alarm. Each alarm can also be assigned to any one of the four opto output modules that
could be used to drive lights and/or horns. (Opto 4 is reserved for shunt calibration.)
The lower third of the Run Display is reserved for alarm messages. The alarm messages
correspond to how the user configured them. Figure 5.3 below is an example display of
alarms 1-2 being configured as high Tension alarms, alarms 3-4 configured as Payout high
and low alarms, alarm 5 configured as a Speed high alarm, and alarm 6 unused. It would be
unlikely to have all these messages on the display at one time, but each has its own location
to prevent them from overwriting each other.
0 MAIN MENU
1.0 SET ALARMS
2.0 CALIBRATION
3.0 DISPLAY
CONFIGURATION
4.0 SYSTEM
CONFIGURATION
MENU
DIAG
ALRM
CALB
RSET
DIAGNOSTICS
SCREEN
2.1 TENSION
CAL METHOD 1
2.2 TENSION
CAL METHOD 2
2.3 TENSION
CAL METHOD 3
3.1 TENSION
DISPLAY SETUP
3.2 SPEED
DISPLAY SETUP
3.3 PAYOUT
DISPLAY SETUP
4.1 ANALOG
INPUT CONFIG
4.2 ANALOG
OUTPUT CONFIG
4.3 ALARM
CONFIGURATION
4.4 SERIAL
CONFIGURATION
LCI-90 Front Panel
Press 2x