Technical Manual RF Socket RF-AxK1ST.01
MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
•
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
10
The following objects are only for the device RF-AZK1St.01 available:
Nr.
Name
Object function
Data type
Direction
Info
Usage
Tip
Objects for the measurement:
8
Active power
meter
Active power
DPT 9.024/
DPT 14.056
send
Socket sends the
current power of the
connected load
Visu, Diagnostic,
Recording
Communication object is shown at
activated power measurement
9
Active power
meter
Current value
DPT 7.012/
DPT 9.021/
DPT 14.019
send
Socket sends the
current of the
connected load
Visu, Diagnostic,
Recording
Communication object is shown at
activated current measurement
10
Active power
meter
Voltage value
DPT 14.027
send
Socket sends the
current voltage at the
connected load
Visu, Diagnostic,
Recording
Communication object is shown at
activated voltage measurement
11
Sub Meter
Active Energy
DPT 13.010/
DPT 13.013
send
Socket sends the
active energy since
the last reset
Visu, Diagnostic,
Recording
Communication object is shown at
activated meters
12
Main Meter
Active Energy
DPT 13.013
send
Socket sends the
active energy since
the last reset
Visu, Diagnostic,
Recording
Communication object is shown at
activated meters
13
Active power
meter
Exceedance of load
DPT 1.001
send
Socket sends
exceedance of load
Visu, Diagnostic,
A tuator…
Communication object is shown at
power measurement and
monitoring of load
14
Active power
meter
Lower deviation of load
DPT 1.001
send
Socket sends lower
deviation of load
Visu, Diagnostic,
A tuator…
Communication object is shown at
power measurement and
monitoring of load
15
Active power
meter
Exceedance of current
DPT 1.001
send
Socket sends
exceedance of
current
Visu, Diagnostic,
A tuator…
Communication object is shown at
current measurement and
monitoring of current