background image

 

Technical

 

Manual

 

Shutter

 

actuator

 

JAL

0X10X.01

 

 

 

 

MDT technologies GmbH  •  

51766 Engelskirchen  •  Papiermühle 1

 

 

Tel.: +49-2263-880  •  Fax: +49-2263-4588  • [email protected]  •  www.mdt.de 

23

 

 

23

 

start

 

driving

 

to

 

reference

 

1

 

Bit

 

starts

 

the

 

driving

 

to

 

reference

 

25

 

state

 

upper

 

position

 

1

 

Bit

 

notify

 

achievement

 

of

 

the

 

upper

 

end

 

position

 

26

 

state

 

lower

 

position

 

1

 

Bit

 

notify

 

achievement

 

of

 

the

 

lower

 

end

 

position

 

Chart

 

11:

 

communication

 

objects

 

absolute

 

position

 

 

The

 

usage/function

 

of

 

this

 

communication

 

objects

 

are

 

explained

 

at

 

the

 

following

 

segments.

 

 

4.3.1

 

Driving

 

to

 

reference

 

The

 

shutter

 

actuator

 

calculates

 

its

 

actual

 

positions

 

from

 

the

 

appointed

 

times

 

for

 

movement.

 

The

 

real

 

times

 

for

 

movement

 

can

 

be

 

corrupted

 

trough

 

outside

 

influences

 

after

 

some

 

time.

 

A

 

driving

 

to

 

reference

 

calculates

 

the

 

appointed

 

time

 

for

 

movements

 

anew

 

and

 

specifies

 

in

 

this

 

way

 

the

 

shutter

 

actuator

 

new

 

times

 

for

 

movement.

 

Based

 

on

 

these

 

new

 

times

 

for

 

movement

 

the

 

shutter

 

actuator

 

can

 

calculate

 

the

 

real

 

position

 

of

 

the

 

shutter/blinds

 

more

 

detailed.

 

The

 

driving

 

to

 

reference

 

is

 

especially

 

useful

 

if

 

someone

 

works

 

very

 

often

 

with

 

commands

 

for

 

absolute

 

positions.

 

Therefore

 

the

 

shutter

 

actuator

 

can

 

calculate

 

the

 

entered

 

position

 

more

 

detailed

 

and

 

drive

 

to

 

this

 

position

 

more

 

precise.

 

The

 

reference

 

run

 

is

 

started

 

through

 

an

 

1

signal

 

on

 

its

 

1

 

bit

 

communication

 

object

 

“start

 

driving

 

to

 

reference”.

 

It

 

is

 

possible

 

to

 

adjust

 

the

 

reaction

 

after

 

the

 

driving

 

to

 

reference

 

by

 

the

 

parameter

 

“reaction

 

after

 

driving

 

to

 

reference”.

 

The

 

shutter

 

actuator

 

can

 

drive

 

to

 

the

 

position,

 

which

 

it

 

had

 

before

 

the

 

reference

 

run,

 

by

 

the

 

setting

 

“drive

 

to

 

former

 

position”.

 

Through

 

the

 

setting

 

“no

 

reaction”

 

the

 

shutter

 

actuator

 

lets

 

the

 

shutter/blinds

 

at

 

the

 

position,

 

which

 

was

 

reached

 

after

 

the

 

end

 

of

 

the

 

reference

 

run.

 

After

 

every

 

transfer

 

of

 

a

 

new

 

parameterization

 

you

 

have

 

to

 

conduct

 

a

 

reference

 

run.

 

This

 

can

 

either

 

manual

 

occurred,

 

that

 

means

 

the

 

upper

 

and

 

lower

 

position

 

are

 

approached

 

ones,

 

or

 

by

 

the

 

object

 

“start

 

driving

 

to

 

reference”.

 

Now

 

the

 

reference

 

run

 

was

 

conducted

 

and

 

the

 

shutter

 

actuator

 

knows

 

its

 

actual

 

state

 

along

 

the

 

driving

 

range.

 

 

4.3.2

 

Commands

 

for

 

absolute

 

positions

 

By

 

the

 

objects

 

for

 

absolute

 

positions

 

you

 

can

 

specify

 

a

 

constant

 

value

 

to

 

the

 

shutter

 

actuator,

 

on

 

which

 

the

 

shutter

 

shall

 

be

 

driven.

 

This

 

value

 

is

 

indicated

 

in

 

percent

 

and

 

has

 

a

 

range

 

from

 

0

100%

 

with

 

every

 

1%

 

step

 

between

 

it.

 

From

 

the

 

indicated

 

percent

 

value

 

the

 

shutter

 

actuator

 

calculates

 

at

 

the

 

next

 

step

 

the

 

real

 

time

 

for

 

the

 

movement

 

of

 

the

 

shutter/blinds

 

based

 

on

 

the

 

appointed

 

times

 

for

 

movement

 

and

 

the

 

actual

 

position.

 

The

 

commands

 

for

 

the

 

absolute

 

position

 

are

 

transmitted

 

to

 

the

 

1

 

byte

 

communication

 

objects.

 

There

 

is

 

an

 

object

 

for

 

the

 

absolute

 

height

 

positions

 

of

 

the

 

driving

 

way

 

at

 

shutter

 

and

 

blinds.

 

Additional

 

there

 

is

 

an

 

object

 

for

 

the

 

opening

 

angle

 

of

 

the

 

blinds

 

at

 

shutters,

 

the

 

object

 

“absolute

 

position

 

of

 

blinds”.

 

At

 

the

 

percentage

 

description

 

corresponds

 

0%

 

always

 

fully

 

opened

 

and

 

100%

 

full

 

closed.

 

 

4.3.3

 

Status

 

objects

 

(actual

 

position/direction)

 

The

 

status

 

objects

 

“Status

 

actual

 

position”

 

and

 

“Status

 

act.

 

position

 

of

 

blinds”

 

conduce

 

the

 

visualization

 

of

 

the

 

absolute

 

position.

 

Both

 

objects

 

indicate

 

the

 

actual

 

state

 

of

 

the

 

height

 

and

 

the

 

opening

 

angle

 

of

 

the

 

blinds,

 

respectively

 

after

 

end

 

of

 

driving.

 

The

 

objects

 

can

 

be

 

used

 

e.g.

 

for

 

Visualization.

 

Summary of Contents for JAL-01UP.01

Page 1: ...51766 Engelskirchen Papierm hle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 12 2011 Technical Manual MDT Shutter Actuator JAL 0206 01 JAL 0410 01 JAL 0810 01 JAL 0410D 01 JAL 0810D 01 JAL...

Page 2: ...objects per channel 12 3 5 Default settings of the communication objects 14 4 Reference ETS Parameter 16 4 1 Channel selection 16 4 1 1 Shutter 17 4 1 2 Blinds 17 4 2 Time for movement 18 4 2 1 Measur...

Page 3: ...Subitem automatic function 31 4 7 2 Automatic blocks 32 4 8 Alert functions superior functions 33 4 8 1 Subitem alert functions 34 4 8 1 Order of alarms 35 4 8 2 Alarm types 36 4 8 3 Periodic observa...

Page 4: ...600W JAL 01UP 01 Shutter Actuator 1 fold 230VAC 6A flush mounted fitting o 1 fold for shutter motors up to 300W 2 2 Usage possible applications The Shutter Actuator actuates shutters as well as blind...

Page 5: ...ies GmbH 51766 Engelskirchen Papierm hle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 5 2 3 Exemplary Circuit diagrams Illustration 1 exemplary circuit diagram shutter actuator 4 fold Illu...

Page 6: ...DC Every channel of the MRDC device contains of two status LEDs the first one for an activated run up command and the second one for an activated move down command By using the four buttons you can ac...

Page 7: ...irection and a switch on delay or a switch off delay for the motor Also you can restrict the driving area or move the shutter by giving absolutely driving commands By using scene or automatic function...

Page 8: ...fter driving to reference limitation of driving area active not active lower limit 0 100 upper limit 0 100 central objects reaction of the central objects for every channel activatable deactivatable s...

Page 9: ...t type Shutter actuator Medium Type Twisted Pair TP Product name addicted to the used type e g JAL 0810 01 shutter actuator 8 fold 8TE 10A Order number addicted to the used type e g JAL 0810 01 2 7 St...

Page 10: ...annel A has the objects 13 to 32 and the channel B the objects 33 to 52 and so on 3 2 Global communication objects For every single channel you can justify whether it shall react on the global objects...

Page 11: ...block A the numbers 5 to 8 are reserved and for the channel B the numbers 9 to 12 are reserved The following illustration shows the communication objects for the both automatic blocks Illustration 5...

Page 12: ...el The numbers follows on the global objects and the objects for the automatic function Therefore these objects have the numbers from 13 So the channel A has the numbers from 13 to 32 and the channel...

Page 13: ...PT 5 001 In Write 20 Status actual position Shows the actual position DPT 5 001 Out Read 21 Status actual position of blinds Shows the actual position of blinds DPT 5 001 Out Read 22 Act Position vali...

Page 14: ...Automatic B Automatic position 3 1 Bit Low X X 12 Automatic B Automatic position 4 1 Bit Low X X 13 Channel A Shutter up down 1 Bit Low X X 14 Channel A Blinds up down stop 1 Bit Low X X 14 Channel A...

Page 15: ...Block 1 Bit Low X X 20 next channel Chart 5 standard settings communication objects You can see the default values for the communication objects from the upper chart According to requirements the prio...

Page 16: ...xt Dynamic range default value comment Channel A D H not active Shutter Blinds Operating mode of the channel Chart 6 possible settings for the channel selection Every of the 1 to 8 available channels...

Page 17: ...tical communication between KNX devices The communication object Blinds up down stop is used to adjust the blinds By calling this object the current movement of the shutter is simultaneous stopped 4 1...

Page 18: ...ble to parameterize the Actuator individually for almost every shutter blind To be sure that the movement function works properly you have to parameterize these times carefully If the channel is selec...

Page 19: ...switch off delay for motors which have time lag after set off Position of blinds at end of driving 0 100 50 only at shutter sets the position of blinds after driving the shutter Short time operation...

Page 20: ...s possible to adjust the step range in a way so that the blinds drive from one final position to the other in a specific number of steps For this way of blind movement you have to set the step time fo...

Page 21: ...ly 4 2 6 Switch on Switch off delay motor Some motors can not bring the full power at the moment of switching it on but first after some milliseconds The time which the motor needs to get the full pow...

Page 22: ...tion after a driving to reference Status objects not active active enables the status objects Status object for visualization Status actual direction Status of movement adjusts the status object for t...

Page 23: ...the reference run by the setting drive to former position Through the setting no reaction the shutter actuator lets the shutter blinds at the position which was reached after the end of the reference...

Page 24: ...utter blinds 4 3 5 Status objects for Visualization The 1 bit status object Status of movement shows that a movement of these shutters blinds is active right now A running movement is indicated by a l...

Page 25: ...n object is displayed for the associated channel Number Name Length Usage 24 Drive to limitation 1 Bit drives to the lower upper limit Chart 13 communication object limitation You set new limits for t...

Page 26: ...Stop 1 Bit stop function for every channel 3 absolute Position 1 Byte absolute command for height at every channel 4 absolute position of blinds 1 Byte absolute command for opening angle of blinds at...

Page 27: ...s activated for this channel the according scene menu is shown At this menu the single scenes can be activated and values scene numbers and the memory function on off can be set Scenes get activated b...

Page 28: ...ave the names A H Every of the 8 scenes can get one of the possible 64 scene numbers The following illustration shows the setting options at the sub item scene channel X scene for the scenes A D and a...

Page 29: ...of this scene This reaction contains a command for an absolute height 0 100 for this channel or additional an absolute position of blinds at a shutter channel see also Chart 17 Every channel can reac...

Page 30: ...x03 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x8A 138 12 0x0B 11 0x8B 139 13 0x0C 12 0x8C 140 14 0x0D 13 0x8D...

Page 31: ...same time through the automatic function for example drive the blinds as well as the shutter and change the opening angle of the blinds The following Illustration shows the activation of the automatic...

Page 32: ...ynamic range automatic function At the subitem for the automatic function you can depose values for 4 different automatic calls The values are absolute values which the channel accepts at the call of...

Page 33: ...objects the deposited values for the automatic function are called It is possible to move all channels of one shutter actuator to their parameterized values with only one command but also to move onl...

Page 34: ...Subitem alert functions If the alert function is activated you can make the following parameterization at the appeared subitem The following illustration shows the drop down menu for the alert functio...

Page 35: ...ock Rain Frost Block Rain Wind Frost sets the priority of the alarms Chart 21 Order of alarms If there are two or more alarms activate to the same time the shutter actuator will evaluate the alarms ac...

Page 36: ...ic observation of the rain alarm setting 0 deactivates the periodic observation Action only when rain alarm is activated no action drive to top drive to bottom Action when rain alarm gets active Frost...

Page 37: ...0 to 120min whereby the setting 0 min sets the periodic observation off The communication object for the respectively alarm must get a signal during the parameterized time otherwise the alarm causes a...

Page 38: ...ion when bus power down up can assign the shutter actuator an action how he shall react to faults of the bus power The following chart shows the dynamic range for this parameter ETS text Dynamic range...

Page 39: ...or every channel by a separately subitem When the block function was activated for a channel a new subitem appears under the according channel called channel X block at the drop down menu The followin...

Page 40: ...rol not active active with activation of the object block universal mode the manual control gets blocked Block up down movement not active active with activation of the object block universal mode the...

Page 41: ...configure the blocking process on your own by using the parameter Blocking universal mode Therefore 5 different options are available Block manual control blocks the manual control at the device for t...

Page 42: ...ion objects per channel Page 12 Illustration 7 Channel selection Page 16 Illustration 8 Time for movement Shutter Page 18 Illustration 9 Time for movement Blinds Page 18 Illustration 10 Objects absolu...

Page 43: ...age 19 Chart 10 Setting range absolute position Page 22 Chart 11 Communication objects absolute position Page 22 Chart 12 Dynamic range limitation Page 25 Chart 13 Communication object limitation Page...

Page 44: ...ge can occur danger for humans animals or material assets Do not let the packaging lying around careless plastic foil bags etc can be a dangerous toy for kids 6 2 Routine disposal Do not throw the was...

Page 45: ...After bus voltage failure or recovery the position of the shutter is selected in dependence on the parameterization The Shutter Actuator is available as modular installation device surface mounted de...

Page 46: ...mechanical 1 000 000 1 000 000 1 000 000 max fuse per channel 16A 10A 10A permitted wire gauge Screw terminal 2 5mm 2 5mm 2 5mm KNX busconnection terminal 0 8mm 0 8mm 0 8mm Operation temperature range...