Technical
Manual
Shutter
actuator
JAL
‐
0X10X.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
13
The
chart
shows
the
communication
objects
per
channel:
Nr.
Function
Usage
Data
type
13
Shutter
up/down
Manual
movement
of
shutter/blinds
DPT
1.007
In,
Write
14
Blinds
Up/Down/Stop
Manual
Movement
of
blinds
(only
at
shutters)
DPT
1.007
In,
Write
14
Short
time
operation
Short
time
movement
of
blinds(only
at
blinds)
DPT
1.007
In,
Write
15
Stop
Stopping
of
the
blind
movement
(only
at
blinds)
DPT
1.017
In,
Write
16
Scene
Calling
of
scenes
DPT
18.001
In,
Write
17
Status
actual
Direction
Shows
actual
direction
DPT
1.008
Out,
Read
17
Status
of
movement
Shows
actual
direction
DPT
1.008
Out,
Read
18
Absolute
position
Move
to
an
absolute
position
DPT
5.001
In,
Write
19
Absolute
position
of
blinds
Move
to
an
absolute
blind
position
DPT
5.001
In,
Write
20
Status
actual
position
Shows
the
actual
position
DPT
5.001
Out,
Read
21
Status
actual
position
of
blinds
Shows
the
actual
position
of
blinds
DPT
5.001
Out,
Read
22
Act.
Position
valid
Shows
whether
the
actual
position
is
between
limits
or
not
DPT
1.002
Out,
Read
23
Start
driving
to
reference
Starting
the
Drive
of
Reference
DPT
1.008
In,
Write
24
Drive
to
limitation
Moves
to
the
actual
selected
limit
DPT
1.008
In,
Write
25
State
upper
position
Notifies
that
shutter/blind
is
at
the
upper
position
DPT
1.001
Out,
Read
26
State
lower
position
Notifies
that
shutter/blind
is
at
the
lower
position
DPT
1.001
Out,
Read
27
Block
absolute
position
mode
Blocks
the
reaction
on
absolute
positions
DPT
1.003
In,
Write
28
Block
universal
mode
Blocks
in
order
to
the
parameterization
DPT
1.003
In,
Write
29
Wind
alarm
Switches
the
wind
alarm
on
DPT
1.005
In,
Write
30
Rain
alarm
Switches
the
rain
alarm
on
DPT
1.005
In,
Write
31
Frost
alarm
Switches
the
frost
alarm
on
DPT
1.005
In,
Write
32
Block
Blocks
the
channel
DPT
1.003
In,
Write
Chart
4:
Communication
objects
per